Uniflair RAN Series Instruction Manual page 27

Table of Contents

Advertisement

Available languages

Available languages

Single-phase voltage regulator
Power Supply
terminal board
The following control devices are found on the control section:
Trimmers: indicated as 'Pn'
Jumpers: indicated as 'Jn'
Led: indicated as 'Dln'
The GREEN DL1 Led signals "delivery of voltage to the load in progress"
The YELLOW DL2 Led signals "Set-point 2 enabling".
The following connection devices are found on the power section:
Power terminal panel: Power supply terminal panel for the connection of the power supply and the load (e.g.
fans)
Control terminal panel: for the connection of control signals (in other words, the two probes/transducers or two
remote control auxiliary voltage regulators)
Precautions:
During re-assembly, always make sure that the cover of the external protection is always tightly closed.
Never modify or damage the equipment's adhesive identification labels
Never force the rotation of the trimmers beyond the mechanical stroke foreseen.
Modify only the positions of the trimmers indicated for adjustment.
Never under any circumstances modify the trimmers marked with a spot of red paint.
RAN-RAL - Rev 1.0. - 11-10-2002 IT - EN
MANUALE DI ISTRUZIONI / INSTRUCTION MANUAL
опубликовано topclimat.ru
RADIATORI REMOTI / DRY COOLERS
Control signal
terminal boards
When Control signal Terminal boards
Contact 9-10 is open, the control is
enabled by Trimmer "P2 + P3"; when
this contact is closed, the control is
enabled by Trimmer "P6 + P7".
26 (32)