Calculating Air Conditioner Distribution; Calculating Simple Distribution - Panasonic CZ-256ESMC1U Operating Instructions Manual

Hide thumbs Also See for CZ-256ESMC1U:
Table of Contents

Advertisement

10 CALCULATING AIR CONDITIONER DISTRIBUTION

The Intelligent Controller calculates energy (electricity and gas) distribution ratios utilizing the
accumulated working time (T/S ON/OFF) or the capacity value of the indoor unit.
* T/S: Thermostat

10.1 Calculating simple distribution

Parameters as listed below are used to calculate simple distribution:
A RHHi: accumulated operation time for indoor unit i (High fan speed)
B RHi: accumulated operation time for indoor unit i (Medium fan speed)
C RLi: accumulated operation time for indoor unit i (Low fan speed)
D SHHi: T/S ON accumulated time for indoor unit i (High fan speed)
E SHi: T/S ON accumulated time for indoor unit i (Medium fan speed)
F SLi: T/S ON accumulated time for indoor unit i (Low fan speed)
G Pi: Capacity of indoor unit i (in kW)
H k: Weighing factor for power consumptions as T/S ON and OFF
I aHH: Weighing factor for High fan speed
J aH: Weighing factor for Medium fan speed
K aL: Weighing factor for Low fan speed
* Accumulated operation time = T/S ON accumulated time + T/S OFF accumulated time
Index of indoor unit i power/gas consumptions is calculated.
Here, "TEi" and TGi" denotes the power and gas consumption indexes of the indoor unit i,
respectively.
When "Object of power distribution calculation" is "T/S ON + OFF time":
The power consumption index is calculated using "Accumulated operation time" and "T/S ON
accumulated time"; the gas consumption index using "T/S ON accumulated time"
• For GHP:
TEi = (RHHi x aHH + RHi x aH + RLi x aL) x Pi
TGi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
• For PAC:
TEi = { (RHHi x aHH + RHi x aH + RLi x aL) /k +
TGi = 0
When "Object of power distribution calculation" is "T/S ON time":
Both the power and gas consumption indexes are calculated using "T/S ON accumulated
time".
• For GHP:
TEi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
TGi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
• For PAC:
TEi = (SHHi x aHH + SHi x aH + SLi x aL) x Pi
TGi = 0
• Weighing by wind speed is not carried out for models with their speed set only as High or only as High and low.
• Distribution ratios are not calculated when you have chosen not to perform distribution ratio calculations. (See "6.3.2
Setting the date, cut-off date, and distribution ratio calculation method")
CZ-256ESMC1U̲改.indb   83
CZ-256ESMC1U̲改.indb   83
(SHHi x aHH + SHi x aH + SLi x aL)} x Pi
Formula 1
Formula 2
Formula 3
83
2011/11/11   11:25:52
2011/11/11   11:25:52

Advertisement