4. Electrical Wiring
All electrical connexions must be performed by a certified electrician and according to local regulation. Using seal connectors and
junction boxes is mandatory.
Use four (4) separate circuit-breakers, two to operate the control panel, one to connect the alarm box and the last one for TLP-FAS
when required. No other household appliance should be connected to these circuit-breakers. They must be used exclusively for the
pump and the alarm box.
The following diagram shows the electrical connections to be made to a treatment system with phosphorus removal unit (DpEC) +
watertight sand filter.
Page 8/14
Owner's manual
20220816
Phosphorus removal unit (DpEC)
Item # 339921