4.2 DLS
Programming
4.3 Panel
Programming
Section
Descriptions
12
4.2.1 [401] Number of Rings to Answer On
This is the number of rings the dialer requires before answering an incoming call. Ring detect
supports Line One only. Programming 000 disables ring detect.
Valid entries are 000-255. Default is 012.
4.2.2 [402] DLS Double Call Window
This is the maximum amount of time the panel will wait between rings to answer an incoming
call with the double call feature. Programming 000 disables this timer.
Valid entries are 000-255 seconds. Default is 060.
4.2.3 [403] DLS Download Enable Timer
In order to program the system from a remote computer, this timer must be enabled with 001-
254 minutes. When programmed, downloading of the system will be allowed until the timer
expires. Uploading of the system information is always enabled.
Valid entries are 000-254. Default is 000.
4.2.4 [421] DLS Access Code
This is the access code required by the dialer in order to allow programming from the down-
loading computer.
The access code must be 4 hexadecimal digits in length.Default is 2600.
4.2.5 [422] DLS Panel ID Code
This is the identification code required by the downloading computer to identify the dialer
module being programmed.
The access code must be 4 hexadecimal digits in length. Default is 2600.
With the addition of the dialer module, the following additional items must be programmed in
the control panel. To program these sections, use of the CFP-550 handheld programmer is
required. Follow the same procedure for programming as indicated in "Programming using the
CFP-550" on page 6. The control panel module address is [02].
NOTE: The installer code will not be required after entering the panel module address.
4.3.1 Zone Programming [001]
This section requires 2 (MR2602) or 5 (MR2605) two-digit entries. Valid entries and descrip-
tion of each entry is shown below.
00 Null Zone
The zone is not used. The zone is not supervised and alarms and troubles are ignored. The End
of Line Resistor is not required.
01 Instant
Both smoke detectors and contact devices cause an instant alarm.
02 Auto Verify
Smoke detectors on that zone will be verified before an alarm is initiated. If this type of alarm
occurs with an alarm present on the system, or the auto-verify timer is active, this zone will
become an instant alarm.
03 Waterflow
Classifies the zone as a waterflow zone. All alarms are instant unless the waterflow delay is
enabled. If the delay is enabled, then when a zone goes into alarm a fixed 60 second delay
starts. At the end of the delay any waterflow zones still in alarm will cause the panel to go into
alarm. The delay will not be restarted on any subsequent waterflow alarms.