4.3.4 Clock Adjust , Section [091]
This 3-digit value is used for any time correction required due to inaccuracies of the crystal
time keeper. The adjustment is made to the last minute before midnight. The default setting is
[060] (seconds), representing no adjustment in the clock time.
Example: If the clock were running fast by 35 seconds a day, set the clock adjust value at [95].
This would ensure that the last minute before midnight would be 95 seconds long, thus
increasing the day by 35 seconds. If the clock were running slow by 45 seconds a day, then
set this value for [15].
WARNING: In order for the test transmission feature in the dedicated dialer to operate prop-
erly, the time and date must be programmed in the panel. The daylight savings and clock
adjust features should be taken into consideration as well.
4.3.5 Time & Date, Section [901]
Enter the system time in 24-hour format. Enter the date with two decimals each for the month
and day and four decimals for the year. (HH:MM MM/DD/YYYY)
Valid entries for the hour are 00-23. Valid entries for the minute are 00-59.
4.3.6 Event Buffer Viewing [902]
When entering this section, the 20 event buffer memory can be viewed. Upon entry, the event
number will be displayed along with the time and date stamp of when that event occurred.
Pressing the [*] key will display the event description. Pressing [*] again will toggle back to the
event number with date and time stamp. Pressing the [<] key or the [>] key will scroll through
the event buffer with event 001 being the first and event 20 being the last.
4.3.7 Module Supervisory Reset [903]
When entering this section, the module supervisory field in the FACP will be erased and all
modules will re-enroll. This will clear any module troubles on the system. This must be done
when removing a module from the system.
4.3.8 Default [999]
When this section is entered, the FACP will be returned to the factory defaults.
4.3.9 Crystal Time Base Options , Section [012] #7
If the option is turned ON, the panel will use the crystal for time keeping. If the option is OFF,
the panel will use AC for time keeping. If crystal time keeping is selected, check whether the
clock needs to be adjusted.
4.3.10 Daylight Savings Options , Section [012] #8
If the option is turned ON, the panel will adjust between daylight and standard times on the
appropriate days (first Sunday in April ahead one hour, last Sunday in October behind one
hour). If the option is disabled, the panel will make no automatic adjustments.
15