Table 2: Contact ID Zone Alarm/Restoral Event Codes
Program any of these codes for zone alarms/restorals when using the standard (i.e. not automatic) Contact ID reporting format:
Medical Alarms
(1)A1 Emergency
(1)A2 Fail to Report In
Fire Alarms
(1)1A Fire Alarm
(1)11 Smoke
(1)12 Combustion
(1)13 Water Flow
(1)14 Heat
(1)15 Pull Station
(1)16 Duct
(1)17 Flame
Table 3: SIA Format Automatic Zone Alarm/Restoral Codes
Zone Definition
[00] Null Zone
No transm.
[01] Fire
FA-ZZ/FH-ZZ
[02] Fire Supervisory
FS-ZZ/FR-ZZ
[03] Sprinkler
SA-ZZ/SH-ZZ
[06] Panic
PA-ZZ/PH-ZZ
[07] Emergency
QA-ZZ/QH/ZZ
ZZ = zones 01-05
26
(1)18 Near Alarm
Panic Alarms
(1)2A Panic
(1)21 Duress
(1)22 Silent
(1)23 Audible
General Alarms
(1)4A General Alarm
(1)4A General Alarm
(1)43 Expansion module failure
(1)44 Sensor tamper
(1)45 Module Tamper
Alarm/Rest.
Trouble/Rest.
Rep Codes*
Rep Codes
No transm.
FT-ZZ/FJ-ZZ
FT-ZZ/FJ-ZZ
ST-ZZ/SJ-ZZ
PT-ZZ/PJ-ZZ
QT-ZZ/QJ/ZZ
firealarmresources.com
24 Hour Non-Fire
(1)51 Gas Detected
(1)52 Refrigeration
(1)53 Loss of Heat
(1)54 Water Leakage
(1)55 Foil Break
(1)56 Day Trouble
(1)57 Low Bottled Gas Level
(1)58 High Temp
(1)59 Low Temp
(1)61 Loss of Air Flow
Zone Definition
SIA Auto
Rep Codes*
[09] Gas
GA-ZZ/GH-ZZ
[10] Freeze
ZA-ZZ/ZH-ZZ
[11] Heat
KA-ZZ/KH-ZZ
[12] Water
WA-ZZ/WH-ZZ
[13] Untyped
UA-ZZ/UH-ZZ
Trouble/Rest.
Rep Codes
GT-ZZ/GJ-ZZ
ZT-ZZ/ZJ-ZZ
KT-ZZ/KJ-ZZ
WT-ZZ/WJ-ZZ
UT-ZZ/UJ-ZZ