DSC CFP-500 Installation Manual page 13

Table of Contents

Advertisement

Reporting Codes, Sections [201]-[270]
Unless you are using Automatic Contact ID or Automatic SIA formats, reporting codes must be
programmed in order for the panel to report events to the central station.
Reporting codes are two digits and can use hexadecimal digits A through F. To disable a report-
ing code, program it as "FF" (default setting) or "00". For a complete description of reporting
codes which can be programmed and lists of automatic Contact ID and SIA format codes,
please see Appendix A: "Reporting Codes".
Event Buffer, Section [902]
The system's event buffer can be viewed in the programming mode. Up to 128 events are
stored in the buffer memory. The event number will be displayed along with the time and date
when the event occurred. Use the [*] key to toggle between the event description and the time
and date stamp. Use the arrow keys (< >) to scroll through the events in memory.
Swinger Shutdown, Section [061]
Swinger shutdown levels determine the number of events the dialer will attempt to communi-
cate before the zone is shut down. A 3-digit entry is required, from 000-255. If 000 is pro-
grammed, the feature will be disabled and all events will be transmitted. A separate swinger
shutdown value is programmed for the following events:
fire zone alarms/restorals
supervisory zone alarms/restorals
zone trouble alarms/restorals
maintenance troubles/restorals
Test Transmissions, Sections [041]-[042]
The dialer can be programmed to send test transmissions to the monitoring station to verify
proper communications.
The Transmission Time of Day determines when the test transmission will occur. The entry is
four digits (HH:MM). To disable the feature, program the time as [9999].
The Test Transmission Cycle will determine the period between test transmissions
NOTE: In order for this feature to function, the panel time and date must be programmed.
See Section 4.2.10 "Time & Date" for more information.
Test Transmission Communicator Options [052] #4
If the Test Transmission Alternates Telephone Lines option is selected, the dialer will alter-
nate between using Telephone Lines 1 and 2 for transmissions, regardless of telephone
line troubles.
If the Test Transmission Uses First Available Line option is selected, the dialer will use
Telephone Line 1 for transmissions. If a trouble exists on Telephone Line 1, the dialer will
switch to Line 2.
Zone Definitions, Section [101]
When using the SIA or Contact ID formats, the control panel zones must be defined in the
dialer module. Once the zones are defined, communications of events will include the correct
zone type. Each zone type is a 2-digit entry.
The available zone types are as follows:
[01] Fire
[02] Fire Supervisory
[03] Sprinkler
[04] Burglary
[05] Holdup
firealarmresources.com
[06] Panic
[10] Freeze
[07] Emergency
[11] Heat
[08] Medical
[12] Water
[09] Gas
[13] Untyped
P
C F P - 5 0 0
R O G R A M M I N G T H E
11

Advertisement

Table of Contents
loading

Table of Contents