Part Numbering Format - Panduit Basic Rack PDU User Manual

Table of Contents

Advertisement

Basic Rack PDU User Manual

Part Numbering Format

This section describes the part numbering format used to identify equipment in the PDU
series. PDU devices are numbered using one of the following formats:
H1M-ABCDEFGHJKLM
l
V1M-ABCDEFGHJKLM
l
The H1M prefix indicates that the model is intended for horizontal mounting.
The V1M prefix indicates that the model is intended for vertical mounting.
The remaining letters in the series represent values as defined in the table below.
Letter
Any numeral, 1-8, indicating the phase wiring for the output circuit break-
A
ers and receptacles
B
Any letter, A-F, indicating input cord configuration
Any numeral, 1-5, and any letter, A-Z, indicating input plug type and
CD*
rated voltage
E
Any numeral, 1-7, indicating the number of output circuit breakers
Any letter, A-Z, indicating the type of overload protection provided for
F
the outlets
Any two numerals, 01-45, indicating the number of output receptacles
GH
provided
The letter 'A' or 'B' followed by any letter, A-Z, indicating the type and
JK
quantity of output receptacles provided
Any numeral, 0-9, or any letter, A-Z, indicating the length of the power
L
supply cord
M
Any numeral, 0-9, indicating the color of the enclosure
* Voltage and amperage ratings:
120V, single-phase, 10A, 12A, 15A, 16A, 20A, 24A or 30A
l
208V, single-phase, 10A, 12A, 13A, 15A, 16A, 20A, 24A, 30A, 48A or 60A
l
230V, single-phase, 16A, 32A, or 48A
l
208V, three-phase (delta), 16A, 20A, 24A, 30A, 40A, 48A, 50A or 60A, 3W + PE
l
208V, three-phase (wye), 16A, 20A, 24A, 30A, 48A or 60A, 3W + N + PE
l
400V, three-phase (wye), 16A, 20A, 24A, 30A, 32A, 48A or 60A, 3W + N + PE
l
- 6 -
What It Represents

Advertisement

Table of Contents
loading