Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN
Item
Filter display delay timer 0000: None
01
Dirty state of filter
02
Central control address 0001: No.1 unit
03
Specific indoor unit
04
priority
Heating temp shift
06
Existence of [AUTO]
0d
mode
Cooling only
0F
10
Type
Indoor unit capacity
11
Line address
12
Indoor unit address
13
Group address
14
Louver type
19
(Air direction adjustment)
Temp difference of
[AUTO] mode selection
1E
COOL → HEAT,
HEAT → COOL
Automatic restart of
28
power failure
Selection of option/Trouble
2A
input (TCB-PCUC2E: CN3)
HA terminal (CN61)
2E
select
31 Ventilating fan control
32 TA sensor selection
33 Temperature unit select 0000: °C (at factory shipment)
Wind direction setting
45
High-ceiling adjustment
5d
(Air flow selection)
Timer setting
60
(wired remote controller)
0002: 2500H
0004: 10000H
0000: Standard
0001: High degree of dirt (Half of standard time)
to
0001: No.1 unit
to
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0000: No priority
0000: 0 °C
0002: +2 °C
to
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0001 : 4-way Cassette
0000: Unfixed
0001: No.1 unit
to
0001: No.1 unit
to
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0001: No.1 unit
to
0001: No.1 unit
to
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0000: Individual
0002: Follower unit of group
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0000: No louver
0004: (4-way Air Discharge Cassette type)
0000: 0 °C
to
(For setup temperature, reversal of COOL / HEAT by } (Data value) / 2)
0000: None
0000: Filter input
0002: None
0000: Usual
0002: Fire alarm input
0000: Unavailable
0000: Body TA sensor
0000 : Smudge reducing position
0002 : Cold draft less position
SET
Type
DATA
0000
Standard (factory default)
0001
High-ceiling (1)
0003
High-ceiling (3)
0000: Available (can be performed) 0001: Unavailable
Description
0001: 150H
0003: 5000H
0128: No.128 unit ... TU2C-Link
0064: No.64 unit ... TCC-Link
0001: Priority
0001: +1 °C
0010: +10 °C
(Up to +6 recommended)
0000 : 1-way Cassette to 0038
0001 to 0039
0128: No.128 unit ... TU2C-Link
0030: No.30 unit ... TCC-Link
0128: No.128 unit ... TU2C-Link
0064: No.64 unit ... TCC-Link
0001: Header unit of group
0001: Swing only
0020: 20 °C
0001: Restart
0001: Alarm input (Air washer, etc.) 0002: None
0001: Leaving-ON prevention control 0000: Usual
0001: Available
0001: Remote controller sensor
0001: °F
HM30
HM40
2.7 m or less
2.9 m or less
3.2 m or less
3.5 m or less
(cannot be performed)
– 81 –
At shipment
0002 : 2500H
0000: Standard
00Un/0099: Unfixed *1
0000: No priority
0002 : +2°C
0000: Provided
0000: Heat pump
0014 : Compact
4-way Cassette
According to capacity
type
00Un/0099: Unfixed *1
00Un/0099: Unfixed *1
00Un/0099: Unfixed *1
0004: (4-way Air
Discharge Cassette
type)
0003: 3 °C
(Ts ±1.5)
0000: None
(HA terminal)
0000: Unavailable
0000: Body TA sensor
0000: °C
0000 : Smudge
reducing position
0000: Standard
HM56
3.2 m or less
3.4 m or less
3.5 m or less
0000: Available