No.
Item
7
Cool air discharge
preventive control
8
Freeze preventive control
(Low temperature release)
Outline of specifications
1) In heating oper
ation, the indoor fan is controlled
based on the detected temperature of TC sensor or
TCJ sensor. As shown below, the upper limit of the
revolution frequency is restricted.
However B zone is assumed as C zone for
6 minutes and after when the compressor activated.
TC
(°C)
TCJ
HH
32
H
30
L
28
UL
26
OFF
20
16
2) When the defrosting operation starts and the four-
way valve of the outdoor unit reverses, the fan of
the indoor unit will stop. (Only when connected to a
compatible outdoor unit)
3) If the fan stops during defrosting operation (A zone),
the louver of the indoor unit will close. This
function can be enabled / disabled by DN setting.
Refer to Item 27 for details.
* In defrost operation, the control value of TC is
shifted by 6°C.
1) The cooling operation (including Dry operation) is
performed as follows based on the detected
temperature of TC sensor or TCJ sensor.
When [J] zone is detected for 6 minutes
(Following figure), the commanded frequency is
decreased from the real operation frequency.
After then the commanded frequency changes
every 30 seconds while operation is performed in
[J] zone.
In [K] zone, time counting is interrupted and the
operation is held.
When [ I ] zone is detected, the timer is cleared
and the operation returns to the normal operation.
If the commanded frequency becomes S0
because the operation continues in [J] zone, the
return temperature A is raised from 5°C to 12°C
until [ I ] zone is detected and the indoor fan
operates with [L] mode.
(°C)
5
2
In heating operation, the freeze-preventive control
works if 4-way valve is not changed and the
following conditions are satisfied.
(However the temperature for J zone dashing
control is changed from 2°C to –5°C.)
<Conditions>
• When
or
is established 5 minutes after
activation.
TCn ≤ TC (n – 1) – 5
TCn < TC (n – 1) – 1 and TCn ≤ TA < 5°C
– 31 –
E zone
D zone
C zone
B zone
A zone
I
A
K
J
Remarks
In D and E zones, the
priority is given to air
volume selection setup
of remote controller.
In A zone while
thermostat is ON,
[PRE-HEAT
(Heating
ready)] isdisplayed.
TCJ:
Indoor heat exchanger
sensor temperature
TCn:
TC temperature when 5
minutes elapsed after
activation
TC (n – 1):
TC temperature at start
time