[F30 trouble]
Is connection
of the occupancy
sensor connector
(CN214) normal?
Is DN code [B5] setup?
Is the Occupancy
sensor unit normal?
Replace the indoor
P.C. board (MCC-1643).
No
Yes
No
Yes
No
Yes
– 64 –
Correct the connector
connection.
By the wired remote
controller, change the
enable DN code [B5] from
[0000] → [0001]
Exchange the Occupancy
sensor unit