ABB PowerValue 11T IN User Manual page 24

Hide thumbs Also See for PowerValue 11T IN:
Table of Contents

Advertisement

24
POWERVALUE 11T IN — 6-10 KVA
09: Battery maximum discharge time setting
Interface
10: Reserved
Interface
11: Reserved
Interface
12: Reserved
Interface
13: Battery voltage calibration
Interface
14: Reserved
Interface
15: Inverter voltage calibration
Interface
Settings
Parameter 3:
000~999: Set the maximum discharge time from 0 min. to 999 min. UPS will shut
down to protect battery after discharge time arrives. The default value is 990 min.
DIS: Disable battery discharge protection and backup time will depend on battery
capacity.
Settings
Reserved
Settings
Reserved
Settings
Reserved
Settings
Parameter 2: Select "Add" or "Sub" function to calibrate battery voltage to
real figure.
Parameter 3: The voltage setting range is from 0V to 5.7V. The default value
is 0V.
Settings
Reserved
Settings
Parameter 2: you may choose Add or Sub to calibrate inverter voltage
Parameter 3: The voltage setting range is from 0V to 6.4V. The default
value is 0V.