U S E R M A N U A L
4 .1 .2 LCD
The LCD shows an overview of the status
of the UPS:
Input
Output
Battery
Load parameters
Working mode
Frequency
Bypass presence
The LCD backlight automatically dims after two
minutes of inactivity (except in cases of a UPS
fault). Press any button to wake up the screen.
A buzzer indicates UPS status. Table 3 lists the
buzzer status meanings.
4.1.2-1
The default LCD
Table 3: Definition of alarms
UPS condition
Buzzer status
Active fault
Continuous
Active warning
Beep every second
UPS on battery: Beep every
4 seconds
Battery
Low battery: Buzzer beeps
every second
Bypass
Beep every 10 minutes
Overload
Beep twice every second
The status screen shows the following
information:
Status summary, including operating mode
and load information
Alarm status, if present (including fault and
warning information)
Battery and charger status (including battery
voltage, charge level and charger status)
For more information on how to use the LCD,
see Chapter 4.6.
17