Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01).
Function
Setting
Number
Value
00
42
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller.
Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function
Setting
Number
Value
00
01
44
02
03
External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function
Setting
Number
Value
00
46
01
02
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired
remote controller" (01). This function will only work if the function setting 42 is set at "Both" (01)
Function
Setting
Number
Value
00
48
01
Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when
the outdoor unit is stopped during cooling operation.
Function
Setting
Number
Value
00
49
01
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
Setting record
Record any changes to the settings in the following table.
Setting Description
Filter sign
Room temperature sensor control for cooling
Room temperature sensor control for heating
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
After completing the Function Setting, be sure to disconnect the power supply and then
reconnect it.
En-10
(♦... Factory setting)
Setting Description
Indoor unit
Both
(♦... Factory setting)
Setting Description
A
B
C
D
(♦... Factory setting)
Setting Description
Operation/Stop mode
(Setting prohibited)
Forced stop mode
(♦... Factory setting)
Setting Description
Both
Wired remote controller
(♦... Factory setting)
Setting description
Disable
Enable
Setting Value

13. TEST RUN

Check items
(1) Is operation of each button on the remote controller normal?
(2) Does each lamp light normally?
(3) Do airflow direction louvers operate normally?
(4) Is the drain normal?
(5) Do not have an abnormal noise and vibration during operation?
Do not operate the air conditioner in test run for a long time.
[Operation method]
• For the operation method, refer to the operating manual.
• T he outdoor unit, may not operate, depending on the room temperature. In this
case, keep on pressing the MANUAL AUTO button of the indoor unit for more than
10 seconds. The operation indicator lamp and timer indicator lamp will begin to flash
simultaneously during cooling test run. Then, heating test run will begin in about three
minutes when HEAT is selected by the remote control operation. (Please follow the
operating manual for remote control operation.)
To end test operation, press the remote controller START/STOP button.
(When the air conditioner is running by pressing the test run button, the OPERATION
Lamp and TIMER Lamp will simultaneously flash slowly.)
[Using the wired remote controller] (Option)
For the operation method, refer to the operating manual.
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button simultaneously for 2
seconds or more to start the test run.
(3) Press the start/stop button to stop the test run.

14. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:
(1) S tarting and stopping method, operation switching, temperature adjustment, timer, air-
flow switching, and other remote controller operations.
(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating manual to the customer.