Fujitsu ASYG07KMTA Service Manual

Fujitsu ASYG07KMTA Service Manual

Indoor/outdoor split type room air conditioner / wall mounted type
Hide thumbs Also See for ASYG07KMTA:

Advertisement

Split type room air conditioner
Wall mounted type
Indoor unit
ASYG07KMTA
ASYG09KMTA
ASYG12KMTA
ASYG14KMTA
CO NT ENT S
SPECIFICATIONS. . . . . . . . . . . . . . . . . . .
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . .
REFRIGERANT SYSTEM DIAGRAM. . . .
CIRCUIT DIAGRAM . . . . . . . . . . . . . . . . .
PCB CIRCUIT DIAGRAM . . . . . . . . . . . . .
ERROR DETECTION . . . . . . . . . . . . . . . .
PARTS (INDOOR UNIT) . . . . . . . . . . . . .
PARTS (OUTDOOR UNIT) . . . . . . . . . . .
ACCESSORIES . . . . . . . . . . . . . . . . . . .
Outdoor unit
AOYG07KMTA
AOYG09KMTA
AOYG12KMTA
AOYG14KMTA
1
3
6
9
10
12
13
21
33

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu ASYG07KMTA

  • Page 1 Split type room air conditioner Wall mounted type Indoor unit Outdoor unit ASYG07KMTA AOYG07KMTA ASYG09KMTA AOYG09KMTA ASYG12KMTA AOYG12KMTA ASYG14KMTA AOYG14KMTA CO NT ENT S SPECIFICATIONS....
  • Page 2 S P E C IFI CAT I ON S FAN MOTOR AND FAN REVOLUTION ELECTRICAL DATA NOISE LEVEL MFD-Z30YB3N INDOOR UNIT ASYG09KMTA High 38 dB 40 dB ASYG07KMTA INDOOR UNIT’S Discrimination OUTDOOR UNIT MFE-W25VA2F Medium 33 dB 34 dB AOYG07KMTA AOYG09KMTA OUTDOOR UNIT’S Discrimination...
  • Page 3 FAN MOTOR AND FAN REVOLUTION ELECTRICAL DATA NOISE LEVEL INDOOR UNIT MFD-Z30YB3N MFD-U50XB3F High 40 dB 43 dB ASYG12KMTA ASYG14KMTA INDOOR UNIT’S Discrimination OUTDOOR UNIT MFE-W25VA2F Medium 35 dB 36 dB AOYG12KMTA AOYG14KMTA OUTDOOR UNIT’S Discrimination INDOOR UNIT Cooling 1,110 rpm 1,250 rpm 30 dB 30 dB...
  • Page 4 D I M E N S I ON S INDOOR UNIT ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA 834 mm 222 mm Drain hose 600 mm Diameter Outside Inside : 13.8 mm 2018.03.01...
  • Page 5 OUTDOOR UNIT 663 mm 290 mm 19 mm 58 mm 16 mm AOYG07KMTA AOYG09KMTA AOYG12KMTA 450 mm 106 mm 2018.03.01...
  • Page 6 799 mm 290 mm 19 mm 68 mm 16 mm 580 mm 109 mm OUTDOOR UNIT AOYG14KMTA 2018.03.06...
  • Page 7 RE FRIGER A N T SY ST EM D IA GR A M Refrigerant direction Cooling ASYG07KMTA / AOYG07KMTA Heating ASYG09KMTA / AOYG09KMTA Heat exchanger (indoor unit) Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8" (9.52 mm)
  • Page 8 Refrigerant direction Cooling ASYG12KMTA / AOYG12KMTA Heating Heat exchanger (indoor unit) Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8" (9.52 mm) Teese tube Muffler 2-way valve 3-way valve Strainer Compressor 4-way valve Expansion valve Strainer Distributor Heat exchanger (outdoor unit) 2018.03.26...
  • Page 9 ASYG14KMTA / AOYG14KMTA Refrigerant direction Heat exchanger Cooling (indoor unit) Heating Refrigerant pipe diameter Liquid : 1/4" (6.35 mm) Gas : 3/8" (9.52 mm) Distributor Muffler 2-way valve 3-way valve Muffler Strainer Compressor 4-way valve Expansion valve Strainer Distributor Heat exchanger (outdoor unit) 2018.03.06...
  • Page 10 Thermistor Thermistor Expansion 4-Way ( Outdoor Fan motor temp. ) valve coil (Pipe) (Discharge pipe) valve coil C I R C U IT D I A GR A M 1 2 3 4 5 6 7 1 2 3 1 2 3 4 1 2 3 4 5 1 2 3 1 2 3 4 5 6 7...
  • Page 11 CONTROL UNIT P CB CI RCUI T DIAGRAM ASYG07KMTA : EZ-01713HSE ASYG09KMTA : EZ-01714HSE ASYG12KMTA : EZ-01715HSE INDOOR UNIT ASYG14KMTA : EZ-01716HSE COMMUNICATION KIT ( OPTION ) UTY-TWBXF2 OUTDOOR UNIT BLACK 3.15A 250V WHITE 2013485-1 CNC01 POWER SOURCE CND01 REMOTE...
  • Page 12 OUTDOOR UNIT INVERTER ASSEMBLY Compressor AOYG07KMTA : EZ-01708HUE Winding Resistance AOYG07,09,12KMTA AOYG09KMTA : EZ-01709HUE 2.190 AOYG12KMTA : EZ-0170AHUE AOYG14KMTA : EZ-0170BHUE AOYG14KMTA 1.975 REACTOR EMI FILTER 13mH 8A ESD-R-16C DC Resistance 415.9m TR-28-16-13 EMI FILTER 1 TURN EMI FILTER GRFC-8 TO INDOOR UNIT W400 GRFC-8...
  • Page 13 E RR O R D ETE C TION Error display Error display OPERATION TIMER ECONOMY OPERATION TIMER ECONOMY Error code Description Error code Description lamp lamp lamp lamp lamp lamp (green) (orange) (green) (green) (orange) (green) Serial communication error Indoor unit error ●...
  • Page 14 P A R TS INDOOR UNIT ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA Ref. Description Part number Remote control (no brand) 9319208008 Remote control holder 9318912005 Bracket panel 9387480009 Electric filter holder 9332911008 Air clean filter assy 9317250009 2018.03.02...
  • Page 15 INDOOR UNIT ASYG07KMTA ASYG09KMTA Wire cover assy ASYG12KMTA ASYG14KMTA Ref. Description Part number Screw cap 9387476002 Under cover L 9387477009 Under cover R 9387478006 Front panel total assy 9387596038 2018.03.02...
  • Page 16 INDOOR UNIT ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA Front panel total assy Grille clamper R Front panel Grille clamper L Ref. Description Part number Panel cover Air filter 9387473018 Front panel B Intake grille assy 9387756036 (FUJITSU) 2018.03.02...
  • Page 17 INDOOR UNIT ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA Ref. Description Part number U/D louver assy 9387479003 Shaft cover 9332861006 Louver spring 9387471007 2018.03.02...
  • Page 18 INDOOR UNIT ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA Control box Control cover Ref. Description Part number Room thermistor holder 9387467000 Thermistor assy 9900627027 2018.03.02...
  • Page 19 INDOOR UNIT ASYG07KMTA Wi-Fi holder PWB holder A ASYG09KMTA ASYG12KMTA ASYG14KMTA Control box PWB holder B Box shield Ref. Description Part number Main PCB (ASYG07) 9710368141 Main PCB (ASYG09) 9710368158 Control box Main PCB (ASYG12) 9710368165 Main PCB (ASYG14) 9710368172...
  • Page 20 Base total assy INDOOR UNIT ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA Ref. Description Part number Cable guide Evaporator total assy (07, 09, 12) 9387593006 Step motor holder assy Evaporator total assy (ASYG14) 9387593013 Step motor Drain pan total assy 9387590005 holder Step motor holder assy 9387714005 2018.03.02...
  • Page 21 INDOOR UNIT ASYG07KMTA ASYG09KMTA ASYG12KMTA Base assy ASYG14KMTA Base total assy Motor cover assy Fan motor Ref. Description Part number Brushless motor (07, 09, 12) 9603614010 Brushless motor (ASYG14) 9603572020 Motor case Crossflow fan assy 9387055016 Motor cover assy Bearing D assy 9333628004 2018.03.02...
  • Page 22 PAR T S OUTDOOR UNIT AOYG07KMTA AOYG09KMTA AOYG12KMTA Ref. Description Part number Protective net assy 9322811004 Outdoor thermistor 9900565053 Drain pipe 9322144003 2018.03.02...
  • Page 23 OUTDOOR UNIT AOYG07KMTA AOYG09KMTA AOYG12KMTA Ref. Description Part number Top panel assy 9322556080 Front panel assy 9322555083 Blow grille 9322135001 Emblem 9387859003 Switch cover assy 9322570000 Cabinet right assy 9322552112 Propeller Fan 9322136008 2018.03.06...
  • Page 24 OUTDOOR UNIT AOYG07KMTA AOYG09KMTA AOYG12KMTA Ref. Description Part number Motor bracket assy (07, 09) 9322553003 Motor bracket assy (AOYG12) 9322553010 Brushless motor 9603553005 Reactor assy 9900583019 Terminal 9900435028 2018.03.02...
  • Page 25 OUTDOOR UNIT AOYG07KMTA Shield panel AOYG09KMTA AOYG12KMTA IPM spacer L PWB Holder Auxiliary plate spacer R Ref. Description Part number Terminal bracket assy Heatsink cover Service unit, Main PCB (07) 9709682326 Service unit, Main PCB (09) 9709682333 Service unit, Main PCB (12) 9709682340 Heatsink 9322418005...
  • Page 26 OUTDOOR UNIT AOYG07KMTA Ref. Description Part number AOYG09KMTA AOYG12KMTA Condenser total assy (07, 09) 9322272010 Condenser total assy (12) 9322273000 S-insulator B 9322387004 S-insulator F 9322388001 S-insulator H 9322389008 2018.03.02...
  • Page 27 OUTDOOR UNIT Ref. Description Part number AOYG07KMTA AOYG09KMTA AOYG12KMTA Compressor assy (07, 09) 9322423009 Compressor assy (12) 9322425003 Solenoid 9970110153 4-way valve assy 9322392008 3-way valve assy 9318254051 Expansion valve coil 9970095153 Pulse motor valve assy 9322403018 2-way valve assy 9322474025 Rubber cushion...
  • Page 28 OUTDOOR UNIT AOYG14KMTA Ref. Description Part number Protective net assy 9322811011 Outdoor thermistor 9900565060 Drain pipe 9322144003 2018.03.02...
  • Page 29 OUTDOOR UNIT Ref. Description Part number AOYG14KMTA Top panel assy 9322556028 Front panel assy 9322555014 Blow grille 9322135001 Emblem 9319151007 Switch cover assy 9322570000 Cabinet right assy 9322552020 Propeller fan 9322136008 2018.01.24...
  • Page 30 OUTDOOR UNIT AOYG14KMTA Ref. Description Part number Motor bracket assy 9322553010 Brushless motor 9603553005 Reactor assy 9900583019 Terminal 9900435028 2018.03.02...
  • Page 31 OUTDOOR UNIT Shield panel AOYG14KMTA IPM spacer L PWB Holder Auxiliary plate spacer R Terminal bracket assy Ref. Description Part number Service unit, Main PCB 9709682357 Heatsink 9322418005 Thermistor assy 9900727062 2017.09.04...
  • Page 32 OUTDOOR UNIT AOYG14KMTA Ref. Description Part number Condenser total assy 9322275004 S-insulator B 9322535009 S-insulator F 9322536006 Hair pin S-insulator H 9322537003 cushion S-insulator V 9323045002 2017.08.30...
  • Page 33 OUTDOOR UNIT AOYG14KMTA Muffler Ref. Description Part number Compressor assy 9322427007 Solenoid 9970110160 4-way valve assy 9322444011 3-way valve assy 9322475008 Expansion valve coil 9970095122 Pulse motor valve assy 9322463005 Rubber 2-way valve assy 9322474001 cushion 2017.09.04...
  • Page 34 A C C E S SO R IE S INDOOR UNIT OUTDOOR UNIT Name and Shape Q’ty Name and Shape Q’ty Remote controller Drain pipe For outdoor unit drain piping work Remote controller holder Cloth tape Tapping screws (Large) Tapping screws (Small) Battery Wall hook bracket...
  • Page 35 1801G4693...
  • Page 36 SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type INVERTER SERVICE INSTRUCTION Models Indoor unit Outdoor unit AS*G07KMTA AO*G07KMTA AO*G09KMTA AS*G09KMTA AO*G12KMTA AS*G12KMTA AO*G14KMTA AS*G14KMTA...
  • Page 37: Table Of Contents

    CONTENTS 1. DESCRIPTION OF EACH CONTROL OPERATION 1. COOLING OPERATION....................01-01 2. HEATING OPERATION....................01-02 3. DRY OPERATION......................01-03 4. AUTO CHANGEOVER OPERATION................01-04 5. INDOOR FAN CONTROL....................01-05 6. OUTDOOR FAN CONTROL..................01-07 7. LOUVER CONTROL..................... 01-08 8. COMPRESSOR CONTROL..................01-09 9.
  • Page 38 3. APPENDING DATA 3-1 FUNCTION SETTING....................03-01 3-1-1 INDOOR UNIT....................03-01 3-1-2 Procedures to change the Function Setting for wireless RC......03-05 3-2 Thermistor Resistance Values..................03-07 3-2-1 INDOOR UNIT....................03-07 3-2-2 OUTDOOR UNIT....................03-07...
  • Page 39: Description Of Each Control Operation

    WALL MOUNTED type INVERTER 1 . DESCRIPTION OF EACH CONTROL OPERATION...
  • Page 40: Cooling Operation

    1. COOLING OPERATION A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is 6°C higher than a set temperature, the compressor operation frequency will attain to maximum performance.
  • Page 41: Heating Operation

    2. HEATING OPERATION A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. * If the room temperature is lower by 6°C than a set temperature, the compressor operation frequency will attain to maximum performance.
  • Page 42: Dry Operation

    3. DRY OPERATION The compressor frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 4. ( Table 4 : Compressor frequency in Dry mode) Operating frequency 07/09/12KMTA 14KMTA...
  • Page 43: Auto Changeover Operation

    4. AUTO CHANGEOVER OPERATION When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the Heating, Cooling, and Monitoring modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. °...
  • Page 44: Indoor Fan Control

    5. INDOOR FAN CONTROL 1. Fan speed ( Table 5 : Indoor fan speed ) Speed (rpm) Operation mode Air flow mode AS*G07KMTA AS*G09KMTA AS*G12KMTA AS*G14KMTA Powerful 1210 1250 1270 1360 Heating 1140 1180 1200 1290 1100 1160 1040 1040 1030 1100 Quiet...
  • Page 45 5. HEATING OPERATION Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig. 5 On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 5.
  • Page 46: Outdoor Fan Control

    6. OUTDOOR FAN CONTROL 1. Outdoor Fan Motor Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor. ( Table 7 : Type of Motor ) AC Motor DC Motor 2.
  • Page 47: Louver Control

    7. LOUVER CONTROL 1. VERTICAL LOUVER CONTROL Fig.9 : Air Direction Range (Function Range) Each time the button is pressed, the air direction range will change as follow: Types of Air flow Direction Setting: ALL MODE : The Remote Controller's display does not change. Use the air direction adjustments within the ranges shown above.
  • Page 48: Compressor Control

    8. COMPRESSOR CONTROL 1. OPEARTION FREQUENCY RANGE The operation frequency of the compressor is different based on the operation mode as shown in the Table 11. (Table 11 : Compressor frequency range) Cooling / Dry Heating Minimum Maximum Minimum Maximum AO*G07KMTA 84rps AO*G09KMTA...
  • Page 49: Timer Operation Control

    9. TIMER OPEARTION CONTROL 9-1 WIRELESS REMOTE CONTROLLER The Table 13 shows the available timer setting based on the product model. ( Table 13 : Timer Setting ) ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER 1. OPEARTION FREQUENCY RANGE OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
  • Page 50 3. SLEEP TIMER If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON. In the cooling operation mode When the sleep timer is set, the setting temperature is increased 1°C.
  • Page 51 9-2 WIRED REMOTE CONTROLLER (OPTION) The table13 shows the available timer setting based on the product model. ( Table13 : Timer Setting ) ON TIMER / OFF TIMER WEEKLY TIMER DAY OFF ON TIMER / OFF TIMER Same to 9-1 1. ON TIMER / OFF TIMER and shown in those. WEEKLY TIMER This timer function can set operation times of the each day of the week.
  • Page 52: Electronic Expansion Valve Control

    10. ELECTRONIC EXPANSION VALVE CONTROL The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the Table15. The compressor frequency, the detected temperature by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor. ( Table15 : The pulse range of the electronic expansion valve control ) Operation mode Pulse range...
  • Page 53: Auto Restart

    14. AUTO RESTART When the power was interrupted by a power failure, etc. during operation, the operation contents at that time are memorized and when power is recovered, operation is automatically started with the memorized operation contents. When the power is interrupted and recovered during timer operation, since the timer operation time is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF) the indoor unit body timer lamp.
  • Page 54: Compressor Preheating

    17. COMPRESSOR PREHEATING When the outdoor heat exchanger temperature is lower than -4°C and the heating operation has been stopped for 30 minutes, power is applied to the compressor and the compressor is heated. (By heating the compressor, warm air is quickly discharged when operation is started.) When operation was started, and when the outdoor temperature rises to -2°C or greater, preheating is ended.
  • Page 55: Outdoor Unit Low Noise Operation

    20. OUTDOOR UNIT LOW NOISE OPERATION The OUTDOOR UNIT LOW NOISE Operation functions by pressing OUTDOOR UNIT LOW NOISE button on the remote controller. This operation stops the PFC control, and changes the Current release operation/release value. OUTDOOR UNIT LOW NOISE Operation mode can be used during cooling, heating and automatic operation. It can not be used in Fan and Dry mode ( Table 20 ) Control / Release...
  • Page 56: Defrost Operation Control

    22. DEFROST OPERATION CONTROL 1. CONDITION OF STARTING THE DEFROST OPERATION The defrost operation starts when the outdoor heat exchanger temperature sensor (Tn) detects the temperature lower than the values shown in Table22. ( Table 22 : Condition of starting Defrost Operation ) Compressor integrating operation time time defrosting after starting operation...
  • Page 57 3. Defrost Flow Chart The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows. Heating operation start : Compressor ON (Not defrosted for 10 minutes) 1st defrost 2nd and later defrost Integrating defrost (Constant monitoring) Compressor integrating Compressor...
  • Page 58: Off Defrost Operation Control

    23. OFF DEFROST OPEARTION CONTROL When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
  • Page 59: Various Protections

    24. VARIOUS PROTECTIONS 1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas temperature. When the discharge temperature becomes higher than Temperature , the compressor frequency is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until the temperature becomes lower than Temperature .
  • Page 60 3. ANTIFREEZING CONTROL (Cooling and Dry mode) The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature . (Table 26 : Anti-freezing Protection Operation / Release Temperature) Outdoor temperature Temperature...
  • Page 61: Trouble Shooting

    WALL MOUNTED type INVERTER 2 . TROUBLE SHOOTING...
  • Page 62: Error Display

    2-1 ERROR DISPLAY 2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY Please refer the flashing pattern as follows. Indoor Unit : AS*G07/ 09/ 12/ 14KMTA The OPERATION, TIMER and ECONOMY lamps operate as follows according to the error contents. Indoor Unit Display Wired Remote Trouble Controller...
  • Page 63 Indoor Unit Display Wired Remote Trouble Controller shooting Error Contents ECONOMY OPERATION TIMER Display (Green) (Orange) (Green) Continuous 4-way Valve Error 9 times 9 times Continuous Discharge Temp. Error 10 times 1 times 02-02...
  • Page 64: Wired Remote Controller Display (Option)

    2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION) For UTY-RNN*M 1. SELF - DIAGNOSIS When " Er " in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authorized service personnel. Unit number (usually 0) Error code SU MOTU WETH FR SA ex.
  • Page 65: Trouble Shooting With Error Code

    2-2 TROUBLE SHOOTING WITH ERROR CODE Trouble shooting 1 Indicate or Display: OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 1 time Flash, Timer lamp: 1 time Flash Serial communication error Economy lamp: Continuous flash. (Serial Reverse Transfer Error) ERROR CODE : [E : 11 ] Detective details:...
  • Page 66 Indicate or Display: Trouble shooting 2 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 1 time Flash, Timer lamp: 1 time Flash Serial communication error Economy lamp: Continuous flash. (Serial Forward Transfer Error) ERROR CODE : [E : 11 ] Detective details: Detective Actuators: When the outdoor unit cannot receive the serial signal from Indoor unit...
  • Page 67 Indicate or Display: Trouble shooting 3 Outdoor Unit : No indication INDOOR UNIT Error Method: Indoor Unit : Operation lamp: 1 time Flash, Timer lamp: 2 time Flash Wired Remote Controller Economy lamp: Continuous flash. Communication Error ERROR CODE : [E : 12 ] Detective Actuators: Detective details: Indoor unit Main PCB...
  • Page 68 Indicate or Display: Trouble shooting 4 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 1 time Flash, Timer lamp: 8 time Flash External communication error Economy lamp: Continuous flash. ERROR CODE : [E : 18 ] Detective Actuators: Detective details: After receiving a signal from the Wi-fi adapter,...
  • Page 69 Indicate or Display: Trouble shooting 5 Outdoor Unit : No indication INDOOR UNIT Error Method: Indoor Unit : Operation lamp: 2 time Flash, Timer lamp: 2 time Flash Indoor unit capacity error Economy lamp: Continuous flash. ERROR CODE : [E : 22 ] Detective Actuators: Detective details: When the total capacity of indoor units does not match...
  • Page 70 Indicate or Display: Trouble shooting 6 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 2 time Flash, Timer lamp: 3 time Flash Combination error Economy lamp: Continuous flash. ERROR CODE : [E : 23 ] Detective Actuators: Detective details: Indoor unit...
  • Page 71 Indicate or Display: Trouble shooting 7 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 3 time Flash, Timer lamp: 2 time Flash Indoor unit Main PCB error Economy lamp: Continuous flash. ERROR CODE : [E : 32 ] Detective details: Detective Actuators: When power is on and there is some below case.
  • Page 72 Indicate or Display: Trouble shooting 8 Outdoor Unit : No indication INDOOR UNIT Error Method: Indoor Unit : Operation lamp: 3 time Flash, Timer lamp: 5 time Flash Manual auto switch Error Economy lamp: Continuous flash. ERROR CODE : [E : 35 ] Detective Actuators: Detective details: Indoor unit Main PCB...
  • Page 73 Indicate or Display: Trouble shooting 9 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 4 time Flash, Timer lamp: 1 time Flash Indoor Room Thermistor Error Economy lamp: Continuous flash. ERROR CODE : [E : 41 ] Detective details: Detective Actuators: Indoor unit Main PCB...
  • Page 74 Indicate or Display: Trouble shooting 10 INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 4 time Flash, Timer lamp: 2 time Flash Indoor Heat Ex. Thermistor Error Economy lamp: Continuous flash. ERROR CODE : [E : 42 ] Detective Actuators: Detective details: Indoor unit Main PCB...
  • Page 75 Trouble shooting 11 Indicate or Display: INDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 5 time Flash, Timer lamp: 1 time Flash Indoor Unit Fan Motor Error Economy lamp: Continuous flash. ERROR CODE : [E : 51 ] Detective Actuators: Detective details: Indoor unit Main PCB...
  • Page 76 Indicate or Display: Trouble shooting 12 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 6 time Flash, Timer lamp: 2 time Flash Economy lamp: Continuous flash. Outdoor unit main PCB error ERROR CODE : [E : 62 ] Detective Actuators: Detective details: Access to EEPROM failed due to some cause after outdoor unit started.
  • Page 77 Indicate or Display: Trouble shooting 13 Outdoor Unit : No indication OUTDOOR UNIT Error Method: INDOOR UNIT Indoor Unit : Operation lamp: 6 time Flash, Timer lamp: 4 time Flash PFC circuit error Economy lamp: Continuous flash. ERROR CODE : [E : 64 ] Detective Actuators: Detective details: When inverter output DC voltage is higher than 415V for over 3 seconds,...
  • Page 78 Indicate or Display: Trouble shooting 14 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 6 time Flash, Timer lamp: 5 time Flash IPM Error Economy lamp: Continuous flash. ERROR CODE : [E : 65 ] Detective details: Detective Actuators: When more than normal operating current to IPM in Main PCB flows,...
  • Page 79 Indicate or Display: Trouble shooting 15 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 7 time Flash, Timer lamp: 1 time Flash Discharge Thermistor Error Economy lamp: Continuous flash. ERROR CODE : [E : 71 ] Detective details: Detective Actuators: When Discharge pipe temperature thermistor open or short-circuit...
  • Page 80 Indicate or Display: Trouble shooting 16 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 7 time Flash, Timer lamp: 3 time Flash Heat Ex. Liquid Outlet Economy lamp: Continuous flash. Thermistor Error ERROR CODE : [E : 73 ] Detective details: Detective Actuators: Outdoor unit Main PCB...
  • Page 81 Indicate or Display: Trouble shooting 17 Outdoor Unit : No indication OUTDOOR UNIT Error Method: Indoor Unit : Operation lamp: 7 time Flash, Timer lamp: 4 time Flash Outdoor Thermistor Error Economy lamp: Continuous flash. ERROR CODE : [E : 74 ] Detective details: Detective Actuators: Outdoor unit Main PCB...
  • Page 82 Indicate or Display: Trouble shooting 18 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 8 time Flash, Timer lamp: 4 time Flash Current Sensor Error Economy lamp: Continuous flash. ERROR CODE : [E : 84 ] Detective details: Detective Actuators: When Input Current Sensor has detected 0A, while Inverter Compressor is...
  • Page 83 Indicate or Display: Trouble shooting 19 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 9 time Flash, Timer lamp: 4 time Flash Over Current Error Economy lamp: Continuous flash. ERROR CODE : [E : 94 ] Detective details: Detective Actuators: "Protection stop by overcurrent generation after inverter compressor start...
  • Page 84 Indicate or Display: Trouble shooting 20 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 9 time Flash, Timer lamp: 5 time Flash Compressor Control Error Economy lamp: Continuous flash. ERROR CODE : [E : 95 ] Detective details: Detective Actuators: If the detected rotor location is out of phase with actual rotor location...
  • Page 85 Indicate or Display: Trouble shooting 21 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 9 time Flash, Timer lamp: 7 time Flash Outdoor Unit Fan Motor Error Economy lamp: Continuous flash. ERROR CODE : [E : 97 ] Detective details: Detective Actuators: When outdoor fan rotation speed is less than 100rpm in 20 seconds...
  • Page 86 Indicate or Display: Trouble shooting 22 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 9 time Flash, Timer lamp: 9 time Flash 4-Way Valve Error Economy lamp: Continuous flash. ERROR CODE : [E : 99 ] Detective Actuators: Detective details: Indoor unit Main PCB...
  • Page 87 Indicate or Display: Trouble shooting 23 OUTDOOR UNIT Error Method: Outdoor Unit : No indication Indoor Unit : Operation lamp: 10 time Flash, Timer lamp: 1 time Flash Discharge Temp. Error Economy lamp: Continuous flash. ERROR CODE : [E : A1 ] Detective details: Detective Actuators: Outdoor unit Main PCB...
  • Page 88: Trouble Shooting With No Error Code

    2-3 TROUBLE SHOOTING WITH NO ERROR CODE Forecast of Cause: Trouble shooting 24 1. Power supply failure 2. External cause Indoor Unit - No Power 3. Electrical components defective Check Point 1 : Check Installation Condition Isn’t the breaker down? Check loose or removed connection cable.
  • Page 89 Forecast of Cause: Trouble shooting 25 1. Power supply failure 2. External cause Outdoor Unit - No Power 3. Electrical Components defective Check Point 1 : Check Installation Condition Isn’t the breaker down? Check loose or removed connection cable. >>If abnormal condition is found, correct it by referring to Installation Manual or Data &...
  • Page 90 Forecast of Cause: Trouble shooting 26 1. Setting/ Connection failure 2. External cause No Operation (Power is ON) 3. Electrical Component defective Check Point 1 : Check indoor and outdoor installation condition Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control. Or, check if there is an open cable connection.
  • Page 91 Forecast of Cause: Trouble shooting 27 1. Indoor Unit error 2. Outdoor Unit error No Cooling / No Heating 3. Effect by surrounding environment 4. Connection pipe / Connection wire failure 5. Refrigeration cycle failure Check Point 1 : Check Indoor unit Does Indoor unit Fan run on High fan? Is Air filter dirty? Is Heat exchanger clogged?
  • Page 92 Forecast of Cause : Trouble shooting 28 1. Abnormal installation (Indoor/ Outdoor) Abnormal Noise 2. Fan failure (Indoor/ Outdoor) 3. Compressor failure (Outdoor) Diagnosis method when abnormal noise is occurred Abnormal noise is coming from Indoor unit. Abnormal noise is coming from Outdoor unit. (Check and correct followings) (Check and correct followings) Is Main unit installed in stable condition?
  • Page 93: Service Parts Information

    2-4 SERVICE PARTS INFORMATION SERVICE PARTS INFORMATION 1 Compressor Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting ) Abnormal noise Stops soon after starting up Does not start up Is there open or loose connection Is there open or loose connection Check if vibration noise by cable?
  • Page 94 SERVICE PARTS INFORMATION 2 Inverter Compressor Check Point 1 : Check Connection Check terminal connection of Compressor (loose or incorrect wiring) Terminal cover opened (BLACK) U(R) V(S) (RED) (WHITE) Check Point 2 : Check Winding Resistance Check winding resistance of each terminal If the resistance value is 0 or infinite, replace Compressor.
  • Page 95 SERVICE PARTS INFORMATION 3 Outdoor unit Electronic Expansion Valve ( EEV ) Check Point 1 : Check Connections Check connection of connector (P30) ( Loose connector or open cable ) EXPANSION VALVE COIL BLUE ORANGE YELLOW WHITE Check Point 3 : Check Voltage from Main PCB. Check Point 2 : Check Coil of EEV Remove connector, check each winding Remove Connector and check Voltage (DC12V)
  • Page 96 SERVICE PARTS INFORMATION 4 Indoor unit fan motor Check Point 1 : Check rotation of Fan Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor) >>If Fan or Bearing is abnormal, replace it. Check Point 2 : Check resistance of Indoor Fan Motor Refer to below.
  • Page 97: Appending Data

    WALL MOUNTED type INVERTER 3 . APPENDING DATA...
  • Page 98: Function Setting

    3-1. FUNCTION SETTING 3-1-1 INDOOR UNIT Remote controller address setting * Because this setting is normally done automatically when 2-wire-type wired remote controller is installed, setting is unnecessary. Multiple indoor units can be operated by using one wired remote controller. Set the unit number of each indoor unit.
  • Page 99 Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature correction values show the difference from the Standard setting "00" (manufactur- er’s recommended value).
  • Page 100 Auto restart Enables or disables automatic restart after a power interruption. Function number Setting value Setting description Factory setting ♦ *Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or external device.
  • Page 101 Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. Function number Setting value Setting description Factory setting l l o ♦...
  • Page 102: Procedures To Change The Function Setting For Wireless Rc

    3-1-2 Procedures to change the Function Setting for wireless RC This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the "FUNCTION SETTING" according to the installation conditions using the remote controller.
  • Page 103 Selecting the Remote Controller Signal Code (1) Press the START/STOP( ) button until only the clock is displayed on the remote controller display. (2) Press the MODE button for at least 5 seconds to display the current signal code. (initially set to (3) Press the SET TEMP.( ) ( ) buttons to change the signal code between Match the code on the display to the air conditioner signal code.
  • Page 104: Thermistor Resistance Values

    3-2. Thermistor Resistance Values 3-2-1 INDOOR UNIT Room temperature thermistor Indoor heat exchanger thermistor Temp ( C) Resistance(k ) Voltage(V) Temp ( C) Resistance(k ) Voltage(V) -10.0 58.2 0.73 -30.0 1131.9 0.21 -5.0 44.0 0.93 -25.0 804.5 0.29 33.6 1.15 -20.0 579.6 0.40...