Two. Function And Technical Parameter - DENAIR DA-30A Installation, Maintenance And Operation Manual

Double screw air compressor
Table of Contents

Advertisement

temperature
Air supplying stop
pressure
Unloading pressure
upper limit
Alter loading time
Alter running time
History fault reset
Current imbalance
degrees
Continuing phase
protection time
Overload restart delay
date of production
Factory number
Two. Function and technical parameters
A. Switching value:nine-way switching value input and ten-way switching value of the relay switch output ;
B. analog quantity:two-way Pt100 Temperature input,two-way 4~20mA transducer inputs and
two sets of three-phase current input.(Mating CT)
C. Sequence input voltage:three phase380V;
D. Controller working power:220V、50Hz、20VA
E. Display range
a) 、oil temperature:—20~150℃;Accuracy :±1℃。
b) 、Air temperature:—20~150℃;Accuracy:±1℃。
c) 、Operating time:0~999999hour。
d) 、Current display range:0~999.9A。
e) 、Pressure:0~1.60MPa. Accuracy ;0.01Mpa。
F. Sequence protection:when protector detects wrong phase ,the acting time≤2s;
G. Motor protection:the controller has over 5 kinds of basic protection functions on main motor and fan motor
a. Rotor locked protection:After starting,When the working current reach to four to eight times of the set
current,the acting time≤0.2s
b. short-circuit protection:If the current is detected to has reached over eight times of the set current,the
acting time≤0.2s;
www.denaircompressor.net
Shanghai Denair Compressor Co.,Ltd.
1.00MPa
0.80MPa
****hour
****hour
****
0006
0005
0000minute
****year**month**day
******
this set temperature,early warn the machine stop.
When the actual air supplying pressure higher than
the set pressure,give stop warning.
In user parameter, the pressure upper limit set should
be less or equal to the set value.
Manufacturers can modify loading operation time
Manufacturers can modify the total operating time
After Inputting history fault password,the faults will
be completely cleared out.
When (the maximum phase current
phase current )
imbalance protection action stops 。When set value
≥15 ,the imbalance protection is useless.
When open phase time set greater or equal with
20seconds,the Phase doesn't work。If imbalance
protection works,the imbalance protection will act。
If motor overloading stop,only start the machine by
time delay no matter power down or reset to avoid
the motor frequent starting.
The production date of the manufacturer input device
The factory number of the manufacturer input device
minimum
et value /10 ) 〕 ,the
(1 + (S
15/48