Figure 6 Terminal Block
10. Insert the ground (bare or green) wire into the terminal
block's (G)round connector.
11. Secure the wire by tightening the ground terminal block
screw to a maximum torque of 16 inch-pounds (1.8 Nm).
12. Insert the Line (black) and Neutral (white) wires into the
terminal block's (L)ine and (N)eutral connectors,
respectively.
13. Secure the wires by tightening the line and neutral terminal
block screws to a maximum torque of 16 inch-pounds (1.8
Nm).
26
Non-sinusoidal
output only.
Non seulement de
sortie sinusoïdale.
REMOTE
POWER
FAULT
PUISSANCE
FAUTE
SHOCK HAZARD
Exposed and uncapped wires are a shock hazard. If you cut the
wires after permanently connecting the AC output wires make
sure that you terminate the wires with a proper wire cap terminal.
Failure to follow these instructions can result in death, serious
injury, or equipment damage.
14. Complete the installation of the strain-relief device.
15. Replace the XPower inverter AC panel and secure the
panel into place using the screws from step #4.
16. Connect the outgoing AC wires to the AC load panel.
WARNING
Xantrex XPower 3000 Installation Guide