Diaphragm Dosing Pump Encore
®
Internal error
The dosing pump carries out a self-check, which switches off the pump if no stroke has been carried out two seconds after motor start-up (e.g. if back pressure is too high) or if the
proximity switch (stroke sensor) does not respond (display E-2). The alarm is reset by pulling out the mains plug.
The functions of the LEDs and built-in warning alarm relay are shown in the following table:
Condition
Power supply absent
Dosing pump running
Dosing pump off (by ON/OFF switch)
Dosing pump off (by external contact)
Level pre-alarm
Level main alarm
Dosing pump fault (proximity switch,
stroke sensor)
Dosing pump fault (current < 4 mA)
*) LED 2 is lit in operating modes 1.1 - 1.64; 0...20 mA and 4... 20 mA

8.6 Other settings

8.6.1 Max. number of strokes
Press and hold the "Mode" and "I/O" keys while applying the voltage, and set the maximum pump stroke frequency using keys ▼ and ▲. When the "Mode" key is released, normal
operation starts.
8.6.2 Warning alarm relay connection
Relay not activated in case of fault or OFF: When voltage is applied, press and hold "Mode" and ▲ keys. Display: "RE0". Relay activated in case of fault or OFF: When voltage is
applied, press and hold "Mode" and ▼ keys. Display: "RE1".

8.7 Factory setting

®
• The initial status of Encore
MB is "OFF".
• Depending on the technical specifications, the maximum stroke frequency is preset (see section 5).
• In case of a fault or "OFF", the warning alarm relay is not activated.

8.8 Connections and cable assignments

Encore
MB control unit
®
l L1 RUN
Motor
L2 STOP
N
PE
k L
Power supply
230 V AC, 50/60 Hz
N
or 120 V AC, 50/60 Hz
PE
m R0 Break contact
Warning alarm relay
(4.9 foot (1.5 m) cable)
Rw Changeover contact
R1 Make contact
28
MB/ME
LED 1
LED 2
LED
Warning alarm relay Display
ON
Extern
Alarm
R0
RW
closed
closed
closed
closed
*)
flashes closed
*)
closed
*)
closed
closed
Standard version
BR (brown)
BK (black)
BU (blue) or GY (grey) WH (white)
GN/YE (green/yellow) GN/YE (green/yellow)
BR (brown)
BU (blue) or GY (grey) WH (white)
GN/YE (green/yellow) GN/YE (green/yellow)
BR (brown)
BU (blue) or GY (grey) WH (white)
BK (black)
R0 RW R1
R0 RW R1
Fault
Operation
R1
-
Number
of strokes
OFF
OFF
Number
of strokes
E - L
E - 2
E - I
CSA version
BK (black)
RD (red)
BK (black)
RD (red)
BK (black)
Operating Instructions
CF.450.410.001.IM.1114

Advertisement

Table of Contents
loading

This manual is also suitable for:

Encore me

Table of Contents