Alarm - UGSI Chemical Feed Encore MB Operation & Maintenance Manual

Diaphragm dosing pump
Table of Contents

Advertisement

Diaphragm Dosing Pump Encore
®
Key
Display Description
Mode + ▼ INT
Manual control
▼ 1.64
Pulse control
▼ 1.32
▼ 1.16
▼ 1.8
▼ 1.4
▼ 1.2
Manual control
The dosing pump delivers a constant flow of chemical per unit time, regardless of the process.
To set this operating mode, proceed as follows:
Press the "Mode" and ▲ or ▼ keys simultaneously until INT is displayed.
1.
2.
Release the "Mode" key. The current stroke frequency is displayed (strokes/min)
Use the ▲ and ▼ keys to change the stroke frequency.
3.
Pulse control
The dosing pump delivers a constant flow of chemical per input pulse. Up to 64 pulses are buffer-stored if the pulse rate exceeds the processing speed. To set the pulse multiplica-
tion/division, simultaneously press the "Mode" and ▲ or ▼ keys until one of the following values is displayed:
• for a ratio of 1:1, i.e. the dosing pump executes one dosing stroke after each pulse,
• 1.2 to 1. 64 for pulse multiplication or
• 2.1 to 64. 1 for pulse division
The "Extern" indicator is lit.
Settings for pulse multiplication and division: 1, 2, 4, 8, 16, 32 and 64.
Example
1. 64
The dosing pump executes 64 dosing strokes after each pulse.
64. 1
The dosing pump executes one dosing stroke after 64 pulses.
Analogue control
The dosing pump doses proportionally to the input signal. To set the operating mode, press the "Mode" and ▲ or ▼ keys simultaneously until one of the following values is dis-
played:
• 0. 20 for 0...20 mA signal or
• 4. 20 for 4...20 mA signal
When the "Mode" key is released, the stroke frequency corresponding to the current is displayed. The "Extern" indicator is lit. If the current is greater than 20 mA (display: OVL) or
less than 4 mA (display: E-I), the alarm indicator is lit, the warning alarm relay switches and the dosing pump stops. The stroke frequency of the dosing pump is proportional to the
input signal.

8.5 Alarm

The dosing pump allows monitoring of the dosing process. An alarm is indicated visually on the display and transmitted by the warning alarm relay.
Alarm LED
Level pre-alarm
flashes
Level main alarm
is lit
CF.450.410.001.IM.1114
MB/ME
Key
Display Description
Mode + ▼ 64.1
Pulse control
▼ 32.1
▼ 16.1
▼ 8.1
▼ 4.1
▼ 2.1
▼ 1.1
▼ 4.20
Analogue control
▼ 0.20
Alarm relay
Pump
switches
continues to operate
switches
stops
Display
Number of strokes
E - L
Operating Instructions