Summary of Contents for JALpower JP5535

  • Page 1 JP5535 1-3KVA USER MANUAL...
  • Page 2 Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.  Never block or insert any objects into the ventilation holes or other openings of the UPS.  Do not place the UPS power cord where it might be damaged. JP5535 True Online 1-3K UPS User Manual...
  • Page 3: Table Of Contents

    6. Controls and Indicators ...................... 12 7. Operation........................... 15 7.1 Operation Mode......................15 8. Battery maintenance ......................16 9. Notes for battery disposal and replacement procedures ............ 17 9.1 Battery Disposal ......................17 JP5535 True Online 1-3K UPS User Manual...
  • Page 4 10.1 Checking UPS status ....................18 10.2 Adjust the factors caused the problem ..............18 Annex A. Intelligent Slot ......................22 Annex B. EPO ........................23 Annex C. Rated Parameters Setting ..................24 JP5535 True Online 1-3K UPS User Manual...
  • Page 6: Electromagnetic Compatibility

    Storing magnetic media on top of the UPS may result in data loss or corruption. Turn off and isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol cleaners. JP5535 True Online 1-3K UPS User Manual...
  • Page 7: Introduction

    Sensitive electronic equipment operates best from sinewave power. For ease of use, the UPS features a LCD display to indicate all information for UPS, and provide kinds of function buttons. 1KVA 2KVA/3KVA Fig 1. Front View JP5535 True Online 1-3K UPS User Manual...
  • Page 8 2KVA 3KVA Fig 2. Rear View RS-232 communication port. DB9 type. EPO. Short to activate. Intelligent slot USB port. B type. Input surge protection slot. Input socket. 1KVA: IEC C14, 2K/3K: IEC C20 JP5535 True Online 1-3K UPS User Manual...
  • Page 9 Introduction Network surge protection. Output Socket External battery port. Optional for standard model. Battery ground Output terminal JP5535 True Online 1-3K UPS User Manual...
  • Page 10: System Description

    AC output power. 3.4 Battery Charger The battery charger utilizes energy from the utility power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the UPS is JP5535 True Online 1-3K UPS User Manual...
  • Page 11: Dc-To-Dc Converter

    UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an audible alarm and illuminated amber Bypass LED. NOTICE:The bypass power path does NOT protect the connected equipment from disturbances in the utility supply. JP5535 True Online 1-3K UPS User Manual...
  • Page 12: Product Specification And Performance

    6A max. 10A max 16A max Voltage 36VDC 72VDC 96VDC Numbers Battery Current 35A max 35A max 37A max Output Voltage 220V/230V/240V Dimension 144*353*222 190*374*336 190*426*336 (WxDxH) mm Standard 10.5 24.5 Weight (kg) Long JP5535 True Online 1-3K UPS User Manual...
  • Page 13 NOTICE:If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following: Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000 Derating Power 100% JP5535 True Online 1-3K UPS User Manual...
  • Page 14: Unpacking And Inspection

    UPS to complete connection. *Except from using socket as output, 3KVA has output terminal as well for load which current is over 10A. JP5535 True Online 1-3K UPS User Manual...
  • Page 15: Operating Procedure For Connecting The Long Backup Time Model Ups With The External Battery

    96VDC/3kVA. Connect in series the batteries of the pack to ensure proper battery voltage. To achieve longer backup time, it is possible to connect multi-battery packs, but the principle of “same voltage, same type” should be strictly followed. JP5535 True Online 1-3K UPS User Manual...
  • Page 16 Notice: DO NOT connect the battery plug to the battery socket of UPS first, otherwise, it may cause electric shock. 4. Connect the external battery plug to the battery socket on the rear panel. JP5535 True Online 1-3K UPS User Manual...
  • Page 17: Controls And Indicators

    1.Press FUNC button to transfer in different menus 2.Press FUNC button for 3 seconds to mute off FUNC 3.Press FUNC and ON/OFF together for 2.5 seconds to set rated parameters when only power supply is on Indicators Description JP5535 True Online 1-3K UPS User Manual...
  • Page 18 Battery indicator: yellow—battery discharge or charged yellow flicker—battery is not connected, battery is low or charger is failure dark—battery is connected Fig 6. LCD Main Menu Description of Main Menu Display Function Submenu JP5535 True Online 1-3K UPS User Manual...
  • Page 19 UPS ID(1-9) in setting mode Load information Load percent(%) Active load(kW) Apparent load(kVA) Protocol code in setting mode Output information Output voltage(VAC) Output frequency(Hz) Output current(A) Note: Press “FUNC” button to see different information. JP5535 True Online 1-3K UPS User Manual...
  • Page 20: Operation

    UPS is working in INVERTER mode. Turn off all of the connected loads before turning off the UPS. The operation above is only suitable for default setting mode. JP5535 True Online 1-3K UPS User Manual...
  • Page 21: Battery Maintenance

    Replace batteries with the same number and same type of batteries.  Do not replace the battery individually. All the batteries should be replaced at the  same time following the instructions of the battery supplier. JP5535 True Online 1-3K UPS User Manual...
  • Page 22: Notes For Battery Disposal And Replacement Procedures

    Remove metal bars which are used to fasten batteries. Replace batteries one by one. Screw metal bars back to UPS. Connect the battery wires one by one. Take care of electrical shock while connecting the last wire. JP5535 True Online 1-3K UPS User Manual...
  • Page 23: Trouble Shooting

    Check if PE on input plug is shorted connected correctly in with UPS rear panel. If not ,contact with distributer or service center. If yes, please check PE wire in input power socket JP5535 True Online 1-3K UPS User Manual...
  • Page 24 “utility fail” after utility failure. UPS output will be off until utility power is on. Fault: Rectifier Bus over voltage, bus Please contact with distributer or fault unbalance, rectifier service center. starting failure, bus JP5535 True Online 1-3K UPS User Manual...
  • Page 25 Battery discharge The battery has not Charge the battery for more than 10 time diminishes been fully charged hours UPS is overload Check the loads and remove some devices JP5535 True Online 1-3K UPS User Manual...
  • Page 26 Please provide the following information when reporting fault UPS: The UPS model and serial NO. The warn and fault code happened Detail of fault, include LED indicates, buzzer beeps, power condition, load capacity and configuration of battery(long backup time model) JP5535 True Online 1-3K UPS User Manual...
  • Page 27: Annex A. Intelligent Slot

    Pin7 to pin5 is NO if battery voltage is low. If not, NC. Normal mode Pin8 to pin5 is NC if UPS works in normal mode. If not, NO. Utility fail Pin9 to pin5 is NO if utility is failure. If not, NC. JP5535 True Online 1-3K UPS User Manual...
  • Page 28: Annex B. Epo

    NO and +24V at normal operation. EPO is activated when shorting NO and +24V. Description of Input Port for Remote EPO Position Name Purpose + 24V +24V, internal power supply EPO_NO EPO is activated when shorting with +24V JP5535 True Online 1-3K UPS User Manual...
  • Page 29: Annex C. Rated Parameters Setting

    Rated Parameters Setting Annex C. Rated Parameters Setting Rated parameters of JP5535 1-3K UPS can be set from panel. Please set rated parameters in according to the following procedures: Start UPS power supply and ensure that rectifier, inverter, bypass and discharge are not working.
  • Page 30 Protocol setting: press ON/OFF to choose mode and enter in protocol setting. Codes are shown in LOAD, press FUNC to change protocol. First code: 0-Modbus, 1-SNT, “CC”- current protocol. Press ON/OFF to choose protocol and display current setting. JP5535 True Online 1-3K UPS User Manual...
  • Page 31 10) If you want to exit from setting mode and give up saving, press ON/OFF and FUNC together for 2.5 seconds when in setting mode. 11) Restart and check if the setting is right. JP5535 True Online 1-3K UPS User Manual...