Paging Console; A 4564 Overview; A 4564 Dip Switch Settings; A 4564 Rear Panel Connections - Redback A 4500C Operating Manual

Evacuation timer with network access
Hide thumbs Also See for A 4500C:
Table of Contents

Advertisement

Redback® A 4500C Evacuation Timer with Network Access

5.0 PAGING CONSOLE

5.1 A 4564 OVERVIEW

The A 4564 paging console provides emergency paging and remote selection of "Alert",
"Evac", "Chime" and "Cancel" modes on the A 4500C.
Note: This unit is NOT recommended for general paging.
Paging is achieved by simply pressing the PTT (push to talk) switch and then speaking.
Paging will override all other functions of the A 4500C including the Alert and Evacuation
modes. If the Alert or Evac modes are initiated while paging is occuring, they will be queued
and played once paging has finished.
Note: The "Lock On" function is not available with this unit.
Caution: If paging is active while an event time is programmed to occur, the event will not
activate. If paging ceases and the finish time for that event hasn't passed, then the event will
activate and run for the remaining programmed time.
Provision has been made for the connection of one only paging console which is wired back
to the A 4500C via CAT5E cabling to the RJ45 "To Paging Console" port on the rear of the
A 4500C (see figure 4.1 for details).
A pre-announcement chime is available at the paging console and through the PA system.
Both of these are set by DIP switches on the rear of the paging console.

5.2 A 4564 DIP SWITCH SETTINGS

DIP switch 1 enables the PA system chime on or off.
DIP switch 2 sets the internal chime on or off
DIP switches 3-4 are not used.
(Max 300 Metres)
IMPORTANT NOTE
Ensure power is switched o when
adjusting DIP switches. New
24V
24V
settings will be e ective when
power is switched back on.
DC In
DC In
DIP Switches
1
2
3
4
5
6
7
8
-
+
1 2 3 4 5 6 7 8

5.3 A 4564 REAR PANEL CONNECTIONS

1
24V DC connector
2.1mm DC jack (centre pin positive).
2
RJ45 connector
For connection back to the A 4565. Either port can be
used.
3
DIP switch options
These switches set the chime options.
4
Chime volume
Use this volume to adjust the chime level.
5
Microphone volume
Use this volume to adjust the microphone level.
18
Redback® Proudly Made In Australia
(Note: DIP 1 must be ON for the internal chime to function).
CAT5e cable
Common
24V Out
Cancel
Evac
Alert
Bell
Mic
Trigger
Trigger
Trigger
Trigger
Volume
To Wall Plate
To Paging
Console
Ensure power is switched off when adjusting DIP switches.
New settings will be effective when power is switched back on.
A 4564 Paging Console
A 4564 Communicator
Lock On
Alert
Evac
Hold buttons for
3 seconds to activate
Page
Chime
Cancel
System Busy
Evac
Alert
Bell
24V Out
24V Out
24V Out
ON
OFF
Battery
Adapter
Backup Battery Holder
Outputs limited to 120mA maximum current draw
Backup
(Use 3V CR2032 Battery Only)
Fig 4.1
SW
1
PA System Chime On
2
Internal Chime On
24VDC In
1
IMPORTANT NOTE:
A 4500B Timer
L
Alert/Evac
Bell
Music
V/Over
Prebell
Level
Level
Level
Level
Level
CR2032
R
Audio
Out
DIP Switches 1-2 Settings
On
O
PA System Chime O
Internal Chime O
ON
1 2 3 4
1 2 3 4
2
3
www.redbackaudio.com.au
Manufactured in Australia
By Altronic Distributors Pty. Ltd.
www.redbackaudio.com.au
Mic
Chime
Volume
Volume
4
5

Advertisement

Table of Contents
loading

Table of Contents