Installation Procedure
• Because your air conditioner contains R-32 refrigerant,
make sure that it is installed, operated, and stored it
in a room whose floor area is larger than the minimum
required floor area specified in the following table:
Minimum required room area (A,m²)
m (kg)
Ceiling-mounted
≤ 1.842
1.843
3.64
1.9
3.75
2.0
3.95
2.2
4.34
2.4
4.74
2.6
5.13
2.8
5.53
3.0
5.92
3.2
6.48
3.4
7.32
3.6
8.20
3.8
9.14
4.0
10.1
4.2
11.2
4.4
12.3
4.6
13.4
4.8
14.6
5.0
15.8
- m : Total refrigerant charge in the system
- A : Minimum required floor area
• IMPORTANT: it's mandatory to consider either the
table above or taking into consideration the local
law regarding the minimum living space of the
premises.
• Minimum installation height of indoor unit is 0.6 m
for floor mounted, 1.8 m for wall, 2.2 m for ceiling.
CAUTION
• 3 m as minimum pipe length: It will reduce noise and
vibration.
• Tighten the nuts to the specified torques.
If overtightened, the nuts could be broken so
refrigerant may leak.
• Protect or enclose refrigerant tubing to avoid
mechanical damage.
NOTE
• The appearance of the unit may be different from the
diagram depending on the model.
20
English
Wall-mounted
Floor-standing
No requirement
4.45
28.9
4.58
30.7
4.83
34.0
5.31
41.2
5.79
49.0
6.39
57.5
7.41
66.7
8.51
76.6
9.68
87.2
10.9
98.4
12.3
110
13.7
123
15.1
136
16.7
150
18.3
165
20.0
180
21.8
196
23.6
213
• You can use the Cool and Heat modes in the following
conditions :
Model
Cool
Outdoor
-10 °C to 46 °C
temperature
- It could take maximum 60 minutes to operate for the
protection of the compressor,if the outdoor temperature
is below -5°C.
Step 7 Optional: Cutting and flaring
the pipes
1 Make sure that you have the required tools available.
(pipe cutter, reamer, flaring tool, and pipe holder)
2 If you wish to shorten the pipes, cut it with a pipe
cutter, taking care to ensure that the cut edge remains
at a 90° angle with the side of the pipe. Refer to the
illustrations below for examples of edges cut correctly
and incorrectly.
90°
3 To prevent any gas from leaking out, remove all burrs
at the cut edge of the pipe, using a reamer.
4 Slide a flare nut on to the pipe and modify the flare.
D
A
Pipe
Flare
Outer diameter (D)
Depth (A)
ø6.35 mm
14 to 18
ø9.52 mm
34 to 42
ø12.70 mm
49 to 61
ø15.88 mm
68 to 82
5 Check that the flaring is correct, referring to the
illustrations below for examples of incorrect flaring.
Heat
-15 °C to 24 °C
Oblique
Rough
Burr
R 0.4 to 0.8 mm
D
L
Flare
Flare dimension (L)
8.7 to 9.1 mm
12.8 to 13.2 mm
16.2 to 16.6 mm
19.3 to 19.7 mm