Mitsubishi Electric AJ65VBTCU-68ADVN User Manual page 21

Analog-digital converter module
Table of Contents

Advertisement

Name and
No.
appearance
The switch to be used for selecting the mode among Ver. remote device station (Ver.
-compatible slave station)/Normal mode/Test mode
Mode select
switch
4)
(Factory-set to
"0")
Transmission
speed setting
switches
5)
Always set the transmission speed within the above range.
The switches are all factory-set to OFF.
Making any other setting than the above will result in an error flickering the "L ERR." LED.
Confirm the transmission speed setting switch numbers on the seal located on the side
face of the connector for analog I/O.
AJ65VBTCU-68ADVN
Ver.1 remote
0: Normal mode
device station
1: Test mode
(Ver.1-
(User range setting 1)
compatible
2: Test mode
slave station)
(User range setting 2)
Ver.2 remote
3: Normal mode
device station
4: Test mode
(Ver.2-
(User range setting 1)
compatible
5: Test mode
slave station)
(User range setting 2)
-
6 to 7: Use prohibited
Set value
4
0
OFF
1
OFF
2
OFF
3
OFF
4
ON
Description
Ver.1 remote
device station
(Ver.1-
compatible
slave station)
Ver.2 remote
device station
(Ver.2-
compatible
slave station)
-
Setting switches
2
1
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
7
AJ65VBTCU-68ADIN
0: Normal mode
1: Test mode
(User range
setting)
3: Normal mode
4: Test mode
(User range
setting)
2, 5 to 7: Use
prohibited
Transmission speed
156kbps
625kbps
2.5Mbps
5.0Mbps
10Mbps