Faults - Possible causes - Solutions

If faults arise in ignition or operations, the burner performs a
"safety stop", which is signalled by the red burner lockout LED.
The operator panel display shows the lockout code.
When the burner starts up again, the red LED goes out.
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row.
WARNING
WARNING
If the burner locks out for a third time, contact the
customer service.
8.1

List of error codes

TRD
Error
P301=0
code
P328>0
0
0
1
0
2
0
3
0
4
1
5
0
6
0
7
0
8
0
9
0
10
0
11
0
13
1
103
0
105
Unlimited
106
0
107
0
120
1
121
0
141
0
151
Unlimited
170
0
191
1
201
1
211
0
221
0
Faults - Possible causes - Solutions
EN67
P301=2
Description
P328>0
0
Unknown fault (internal error)
3
Flame fault
0
Parasite light detected
3
General flame fault during ignition
1
Flame failure during operation
3
No flame signal during the first safety time
3
Flame signal disappears during the stabilisation time
3
No flame signal during the first safety time
0
No flame signal at the end of the second safety time
0
No flame signal during the first safety time
0
No flame signal at the end of the first safety time
Monitoring the parasite flame does not last for the required 5
0
seconds
0
The flame signal appears during ignition (pilot burner)
0
Various data invalid
0
Data curve invalid or unavailable
0
Difference between the value of the parameters HP and UP.
Possible cause of the error:
You have loaded an abnormal data set (unprotected) and there has
been an error during the data transfer. The data set has not been
saved correctly.
0
Configuration not valid; contact the After Sales Service
1
Various operating modes on both controllers
0
Out of range correction.
0
Feedback speed variation too broad.
The set of parameters is based on an obsolete or invalid factory set-
ting.
Update the factory setting of the BT300.
The recirculation damper is still OPEN 240 seconds after recircula-
3
tion reset was switched off (OFF).
0
LDR flame sensor short-circuit
1
First monitoring band has been exceeded for too long: channel
1
First monitoring band has had a short-circuit for too long: channel
0
Second monitoring band has been exceeded for too long: channel
Second monitoring band has had a short-circuit for too long: chan-
0
nel
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
DANGER
manual and in compliance with the standards and
regulations of current laws.
41
GB
D1
D2
Curve set /
Fuel num-
ber
Parameter
No.
Channel
Channel
Channel
Channel
Channel
Channel
Channel
20168262

Advertisement

Table of Contents
loading

This manual is also suitable for:

20166921

Table of Contents