4.7

Firing rate

The maximum output should be chosen within area A)(Fig. 2) of
the diagram.
The minimum output must not be lower than the minimum limit
of the diagram.
The firing rate was obtained at an ambient tem-
perature of 20°C and an atmospheric pressure of
1000 mbar (approx. 100 m above sea level), and
with the combustion head adjusted as shown on
WARNING
WARNING
page 22.
12
11
10
9
8
7
6
5
4
3
2
1
0
-1
kg/h
kW
4.8

Test boiler

The firing rates were established in special test boilers, according
to EN 676 regulations.
In Fig. 3 you can see the diameter and length of the test combus-
tion chamber.
Example:
Output 756 kW (650 Mcal/h): diameter 60 cm, length 2 m.
20168262
Technical description of the burner
29
12
21
37
200
100
300
400
For the operation inside the area B)(Fig. 2)
remove the gas nozzle as shown ("Removing
the nozzles" on page 22).
WARNING
WARNING
A
A
B
46
54
62
71
500
600
700
800
Heat output
10
GB
20094439
79
87
96
104
900
1000
1100
1200
1300
D715
Fig. 2
Fig. 3