6.3.7.1. Freeze Limits
This setting controls the temperature level to which the loop liquid can drop before
the Geo HP unit will stop operating. See the Geo HP Installation Instructions for
more details. Typically, 26_F is chosen for open- - loop systems using untreated
water; and 15_F is chosen for closed- - loop systems using glycol or other anti- - freeze
solutions. After the selection is made, touch SAVE.
Freeze Limits: 26_F or 15_F
S
Default = 26_F