Siemens RDS110 User Manual page 36

Smart thermostat
Hide thumbs Also See for RDS110:
Table of Contents

Advertisement

6
Operating the thermostat on the device
Advanced settings
36 | 59
No. Application
Descriptions
settings
38. Heating
Indicates a different
control loop
time for PWM (Pulse
Width Modulation)
pulse periods. You
can select the
default setting to let
the system configure
the most suitable
heating controller
settings based on
your selected
equipment type.
39. Floor
Floor temperature
temperature
limit for electric floor
limit
heating
40. Optimum
Pre-heats the room
start control
in an optimum way
so that you can get
the scheduled
temperature setpoint
at your scheduled
occupied time. You
can choose "Warm-
up gradient" to
manually define the
warm-up speed, or
choose "Self-
adaptive" to let the
thermostat learn and
decide the warm-up
speed.
41. Warm-up
The warm-up speed
gradient
that you set to pre-
heat the room.
Factory
Range
settings
Default
Slow
Medium
Default
Fast
2-position
Self-
adaptive
35...60 ° C Valid only if
40 ° C
Warm-up
Warm-up
gradient
gradient
Self-
adaptive
0...120 mi
30 min/K
n/K
A6V10877569_en--_f
Dependencies
N/A
you've
selected the
equipment type
as "Electric
floor heating"
and enabled
the floor
temperature
input in
Changing
system setup
[➙ 37].
Visible only if
you've
activated the
optimum start
control settings
in Changing
system setup
[➙ 37].
Valid only if
you've
activated the
optimum start
control settings
in Changing
system setup
[➙ 37] and
selected
"Warm-up
gradient" for
Application
setting No.40