Siemens RDS110 User Manual page 30

Smart thermostat
Hide thumbs Also See for RDS110:
Table of Contents

Advertisement

6
Operating the thermostat on the device
Advanced settings
Heating setpoints
30 | 59
No. Application
Descriptions
settings
11. Comfort
The default heating
setpoint for "Comfort"
heating
setpoint
defined in a
scheduler. This
setpoint must be
higher than that for
protection.
12. Economy
The default heating
heating
setpoint for
"Economy" defined in
setpoint
a scheduler. This
setpoint must be
higher than that for
protection.
13. Unoccupied
The default heating
heating
setpoint for
"Unoccupied" mode.
setpoint
This setpoint must be
higher than that for
protection.
14. Protection
The default minimum
heating
heating setpoint to
setpoint
maintain when you
switch the thermostat
to "OFF" under
"Operating mode".
15. Max.
The default maximum
heating
heating setpoint if the
setpoint
thermostat is not
switched to "OFF". If
it is "OFF", the
maximum heating
setpoint is then the
heating protection
setpoint.
Factory
Range
settings
0...50 ° C
21 ° C
0...50 ° C
19 ° C
0...50 ° C
15 ° C
0...50 ° C
7° C
>
0...50 ° C
35° C
A6V10877569_en--_f
Dependencies
N/A
N/A
N/A
This setpoint is
valid only if you
keep the
default
Protection
option for
Application
setting No. 37.
The heating
protection
setpoint is valid
only if you
keep the
default
Protection
option for
Application
setting No. 37.