Operation
Settings menu
The factory settings are highlighted in the following table.
Meu item
Hydraulics
Low-loss header
DHW configuration
HC1 configuration
Pump config.
Heating
Max. heat output
Standby time
Anticyc. temp. off
Anticycle temp. on
Hot water
Max. DHW output
DHW circ. pump
Cycle circ. pump
TD-Temperature
Start TD
Stop TD
Pump
Pump ctr. mode
Min. output
28
Settings/adjustment range
• Off
• NTC on device
• NTC on module
• NTC off
• Not installed
• 3-way valve installed
• Cyl. prim. pump inst. after low loss hdr.
• Cyl. primary pump installed
• Not installed
• Dedicated pump inst. after low loss hdr.
• Heating pump
• 50 100%
• 5 ... 10 ... 60 min
• 2 ... 6 ... 15 K
• -15 -6 ... 2 K
• 50 100%
• Off
• On
• 1 x 3 minutes/h
• 2 x 3 minutes/h
• 3 x 3 minutes/h
• 4 x 3 minutes/h
• 5 x 3 minutes/h
• 6 x 3 minutes/h
• Permanent
• 60 70 ... 80 °C
• Start now?
• Cancel now?
• Energy saving
• Heat demand
• 10 ... 100 %
Remark/restriction
Connection of temperature sensor on the low loss header
• Low loss header not installed in the system
• Low loss header installed, temperature sensor
connected to wall mounted boiler
• Low loss header installed, temperature sensor
connected to heating circuit module
• Low loss header installed, but no temperature sensor
connected
Maximum released heat output [%].
On natural gas devices:
▶ Measure the gas rate.
▶ Compare the measurement obtained with the setting
tables ( Chapter 16.5, page 49).
▶ Correct deviations.
The time interval specifies the minimum waiting time
between switching on the burner and switching it on
again.
The difference between the current flow temperature and
the set flow temperature until the burner is switched off.
The difference between the current flow temperature and
the set flow temperature until the burner is switched on.
Maximum approved DHW output [%].
The DHW circulation pump goes into operation 1 ... 6
times per hour for 3 minutes, or into continuous
operation.
DHW temperature during thermal disinfection.
Start thermal disinfection.
Cancel thermal disinfection.
• Save energy: intelligent shutdown of heat pump for
heating systems with weather-compensated
controller. The heating pump is only switched on if
required.
• With heat demand: the flow temperature controller
switches the heating pump. If there is heat energy
demand, the heating pump starts up with the burner.
Pump output at minimum heat output. Only available if
Pump range map is set to 0.