Cover Replacement - Intec AIRSENSE I-310e Operator's Manual

Microprocessor-based, infrared environmental co2 sensor
Table of Contents

Advertisement

I-310e – UserManual
1. Be sure that the output select jumper is set correctly
2. Momentarily closing JP5 will set the unit to full scale
3. Remove the shorting block from JP4 and restore it to its

Cover Replacement

Engage the top center of the cover under the latch at the top
of the base, then press the bottom of the cover onto the base
until it latches.
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. |
for voltage or current output. If this is not done first,
the following check may produce incorrect results.
Note whether the shorting block at jumper JP5 is
covering both pins or only a single pin, then borrow
the shorting block and slide it over the two pins of
jumper JP4 (see Figure 2). The display (if present) will
show 'SEL'
output (10V or 20mA). Do not press the buttons on the
unit as this will affect the output calibration.
If the receiving device does not indicate a full scale
reading after JP5 is closed, verify that the wiring is
correct.
original position at jumper JP5. The Model I-310e will
reset and it's output now corresponds to the actual
detected CO 2 concentration.
DCS, Inc. | PRE 200217 | Page 9 of 17
©