5.2 Installation Precautions

Please install the microinverter and all DC connections under a PV module to avoid direct sunlight, rain exposure, snow
accumulation, UV etc. Allow a minimum of 2 cm of space around the microinverter enclosure to ensure ventilation and heat
dissipation.
Warning! Be sure to verify the following before installing the microinverter system:
Verify that the voltage and current specifications of the PV module match those of the microinverter.
The maximum open circuit voltage rating of the PV module must within the operating voltage range of the
microinverter.
The maximum current rating at MPP is recommended to be equal to or less than the maximum input DC current. The
maximum short circuit current must be equal to or less than the maximum input DC short circuit current.
The output DC power of PV module is NOT recommended to exceed 1.35 times the output AC power of the
microinverter. Refer to Warranty Terms & Conditions for more information.