6. CHARACTERISTICS OF FAN

(1) Duct connected-High static pressure type (FDU)
・Characteristic FAN (1) shows air flow vs. External Static Pressure (E.S.P.) range where settings of E.S.P. are maximum E.S.P.
(SW8-4 OFF : 150Pa, SW8-4 ON : 200Pa) , rated E.S.P., and minimum E.S.P. (SW8-4 OFF : 80Pa, SW8-4 ON : 10Pa)
・Characteristic FAN (2) shows air flow vs. E.S.P. curve when set fan tap is set P-Hi with each setting of E.S.P. by remote control.
・External Static Pressure (E.S.P.) can be set by wired remote control.
・You can set required E.S.P. by wired remote control which calculate it with the set air flow rate and pressure loss of the duct connected.
Models FDU45KXE6F-W, 56KXE6F-W
■SW8-4 : OFF (Range of use limitation : Setting 80Pa-150Pa)
Characteristic FAN (1)
In case actual E.S.P. correspond setting of E.S.P.
220
200
180
160
140
120
100
80
60
Lo
Lo
40
Lo
20
0
6
8
■SW8-4 : ON (Range of use limitation : Setting 10Pa-200Pa)
Characteristic FAN (1)
In case actual E.S.P. correspond setting of E.S.P.
220
200
180
160
140
120
100
80
Lo
60
Lo
40
Lo
20
Lo
0
6
8
P-Hi
Setting 150Pa
Setting 120Pa
P-Hi
Hi
P-Hi
Hi
Me
Me
Setting 80Pa
Hi
Me
10
12
13
14
Air flow (m
/min)
3
P-Hi
Setting 200Pa
Setting 120Pa
P-Hi
Hi
Me
Setting 60Pa
Hi
P-Hi
Me
Me
Hi
Setting 10Pa
P-Hi
Hi
Me
10
12
13
14
Air flow (m
/min)
3
Characteristic FAN (2)
220
200
180
160
140
120
100
80
60
40
20
0
16
11
Characteristic FAN (2)
220
200
180
160
140
120
100
80
60
40
20
0
16
11
39
-
-
'21 • KX-T-386
Range of approvable air flow rate
12
13
14
Air flow (m
/min)
3
Range of approvable air flow rate
12
13
14
Air flow (m
/min)
3
15
15