2. Detailed Settings Function
List of Detailed Setting Items
Item code
Item
No.
0000
0003
Type
0007
0011
0001
0007
Indoor unit
capacity
0012
0018
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
System
address
0030 Unit No. 30
0099 Not set
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
Indoor unit
address
0064 Unit No. 64
0099 Not set
0000 Individual (1:1 = Indoor unit with no group wiring)
0001 Main unit (One of the group-control indoor units)
Group control
address
0002 Sub unit (All group-control indoor units except for main unit)
0099 Not set
–010 Shifts intake temperature by –10°C.
–009 Shifts intake temperature by –9°C.
Cooling
–001 Shifts intake temperature by –1°C.
intake
0000 No intake temperature shift
temperature
0001 Shifts intake temperature by +1°C.
shift
0009 Shifts intake temperature by +9°C.
0010 Shifts intake temperature by +10°C.
0000 Function disabled
Automatic
stop time
0001 Stops automatically 5 minutes after operation starts.
after
0002 Stops automatically 10 minutes after operation starts.
operation
start
0123 Stops automatically 615 minutes after operation starts.
* Can be set
in 5-minute
0124 Stops automatically 620 minutes after operation starts.
units.
0125 Stops automatically 625 minutes after operation starts.
Description
No.
1-Way Air Discharge
0001
Semi-Concealed (A)
1-Way Air Discharge
0005
Semi-Concealed Slim (L)
Ceiling-Mounted (T)
0008
Concealed Floor
Standing (FM)
22 (Type 74)
0003
45 (Type 164)
0009
80 (Type 254)
0015
(Except FR254, FMR254)
160 (Type 604)
0021
Setting data
Description
4-Way Air Discharge
Semi-Concealed (X, XM)
Concealed-Duct (U, US)
Wall-mounted (K)
28 (Type 94)
56 (Type 184)
106 (Type 364)
224 (Type 764)
4 - 5
W-2WAY ECO-i SYSTEM
Remote Controller Functions
No.
Description
2-Way Air Discharge
0002
Semi-Concealed (S)
Concealed-Duct High
0006
Static Pressure (D)
0010
Floor Standing (F)
0005
36 (Type 124)
71 (Type 254)
0011
For FR254 and FMR254
0017
140 (Type 484)
0023
280 (Type 964)
4