Sanyo 2-WAY ECO-i SPW-C0705DXHN8 Service Manual page 95

Multi system
Hide thumbs Also See for 2-WAY ECO-i SPW-C0705DXHN8:
Table of Contents

Advertisement

1. Simple Settings Function
List of Simple Setting Items
Item code
Item
Filter sign ON time
(fi tlter life time)
Degree of fi lter fouling
Central control
address
Operating mode
priority change
Fan speed when
heating thermostat is
OFF
Heating intake
temperature shift
Electric heater
installation
Humidifying when
heater thermostat is
OFF
Permit/prohibit
automatic
heating/cooling
Cool-only
NOTE
In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF unless a
vaporizing humidifier is used.
Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
Do not change any setting data that does not appear in this list.
The 10-hp 4-way ceiling cassette has 2 indoor unit addresses. Set both of them.
No.
0000
Not displayed
0001
150 hours
0002
2,500 hours
0003
5,000 hours
0004
10,000 hours
0005
Use the fi lter clogging sensor.
0000
Standard (setting at time of shipping)
Highly fouled
0001
(Filter sign ON time is reduced to one-half the set time.)
0001
Central control address 1
0002
Central control address 2
0003
Central control address 3
0064
Central control address 64
0099
No central control address set (setting at time of shipping)
0000
Normal (setting at time of shipping)
0001
Priority
Compressor ON
0000
MED 1 min., LO 3 min.
0001
MED
0002
LO
0004
MED 1 min., LO 3 min.
0005
MED
0006
LO
0000
No shift
0001
Shifts intake temperature 1°C down.
0002
Shifts intake temperature 2°C down.
0003
Shifts intake temperature 3°C down.
0004
Shifts intake temperature 4°C down.
0005
Shifts intake temperature 5°C down.
0006
Shifts intake temperature 6°C down.
0000
No heater
0001
Heater installed
0000
No (setting at time of shipping)
0001
Yes
0000
Permit
0001
Prohibit
0000
Normal
0001
Cool only (Set "1" for item code OD.)
4 - 3
W-2WAY ECO-i SYSTEM
Remote Controller Functions
Setting data
Description
Compressor OFF
LO
LO
LO
MED
MED
MED
4