4. Backup Operation
4-2-2. Backup operation by setting the failed compressor not to operate
Backup operation settings for each compressor
INV compressor
OK
OK
OK
Failed
2
Failed
Failed
AC1 compressor
AC2 compressor
OK
Failed
Failed
OK
OK
Failed
Outdoor Unit Repair Procedures
Setting for backup operation
Failed
DIP switch S010:
Turn BACK UP and AC2 ON.
OK
DIP switch S010:
Turn BACK UP and AC1 ON.
Failed
DIP switch S010:
Turn BACK UP, AC1, and AC2 ON.
OK
DIP switch S010:
Turn BACK UP and INV ON.
Failed
DIP switch S010:
Turn BACK UP, INV, and AC2 ON.
OK
DIP switch S010:
Turn BACK UP, INV, and AC1 ON.
2 - 8
W-2WAY ECO-i SYSTEM