Installation Instructions

4 Installation

4.1 Preparation

1.
Ensure you have the following parts:
No.
Name
1
Control box
2
Screws
3
Anchors
4
Connective wires group
5
5m connective wires group
Table 1
2.
Prepare the following tools:
No.
Name
1
Switch box
2
Wiring tube (insulating sleeve and tightening screw)
Table 2
3.
Select installation location. DO NOT install the 24V INTERFACE near
fl ammable liquids or gases such as gasoline or hydrogen sulfi de. Doing so
creates a fi re hazard.

4.2 Installation Process

1.
Remove the cover of the 24V INTERFACE. Remove the four screws of the
24V INTERFACE with a screwdriver. Lift the top cover as shown in Fig. 3.
Figure 3
Minimum free space required around the product is 7" (180 mm).
2.
Mount the back plate of the 24V INTERFACE on the wall. Mount the 24V
INTERFACE vertically and fasten the back plate to the wall with 3 screws
(M4 x20) and anchors (see Fig. 4).
6 |
Quantity
Remarks
1
M4 x20
3
(For mounting on the wall)
3
For mounting on the wall
2
For connecting the sensor
1
Quantity
1
1
Figure 4
    P lace the unit on a fl at surface. Be careful not to distort the back plate of
the 24V INTERFACE by over tightening the screws.
When installed vertically, the direction of the arrow must be up.
3.
Wiring: please refer to following pages for model specifi c wiring procedures.
4.
Reinstall the cover and fasten screws (see Fig. 5).
Figure 5
    S ystem Confi guration
Thermostat should be configured for use with a conventional
system.
The remote controller, wiring controller, central controller and
WiFi cannot be used with this control box at the same time.
Only the Swing and LED function can be used.
Connection wiring specifi cation
Name
Outdoor 1,2,3
Indoor 1,2,3
R,C
Y/W/G/G1/G2/G3/Dry
Table 3
Bosch Climate 5000 Series 24 Volt Interface (06.2022)
Back plate
Screws (M4×20)
Size
Refer to outdoor connective wires size
Refer to indoor connective wires size
18AWG (minimum)
24AWG (minimum)