Cisco IOS image (12.2(18)SXE5 or greater). See your Cisco IOS release notes for the exact release information. Note The CompactFlash adapter is not supported in systems that run the Catalyst operating system. Americas Headquarters: Cisco Systems, Inc., 170 West Tasman Drive, San Jose, CA 95134-1706 USA “Safety Warning Translations”...
Gebruik het nummer van de verklaring onderaan de waarschuwing als u een vertaling van de waarschuwing die bij het apparaat wordt geleverd, wilt raadplegen. BEWAAR DEZE INSTRUCTIES Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note CompactFlash Adapter 78-17277-05...
å forhindre ulykker. Bruk nummeret i slutten av hver advarsel for å finne oversettelsen i de oversatte sikkerhetsadvarslene som fulgte med denne enheten. TA VARE PÅ DISSE INSTRUKSJONENE Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note 78-17277-05...
Använd det nummer som finns i slutet av varje varning för att hitta dess översättning i de översatta säkerhetsvarningar som medföljer denna anordning. SPARA DESSA ANVISNINGAR Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note 78-17277-05...
Brug erklæringsnummeret efter hver advarsel for at finde oversættelsen i de oversatte advarsler, der fulgte med denne enhed. GEM DISSE ANVISNINGER Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note 78-17277-05...
ROMMON Image” section on page Upgrading and Verifying the SP ROMMON Image In order to utilize the SP CompactFlash adapter, your Supervisor Engine 720 must have SP ROMMON Release 8.4(2) or a later release installed on it. The upgrade task description is based on the Supervisor Engine 720 installed in a 9-slot chassis currently Note running ROMMON from its S (Gold) region;...
Page 9
Verify the SP ROMMON version by entering the remote command switch show version | include Step 8 ROM command. You should see “ROM: System Bootstrap, Version 8.4(2).” Note 78-17277-05 Installing the SP Bootflash Memory Upgrade Kit Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note...
Page 10
Loosen the two captive screws on the supervisor engine that is to be removed. Step 5 Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note “Attaching Your ESD Grounding Strap” section on page 24 78-17277-05...
Page 11
Grasp the edges of the supervisor engine, and slide the supervisor engine straight out of the slot. Do not touch the module circuitry. Immediately place the supervisor engine on an antistatic mat or antistatic foam. Step 7 78-17277-05 Installing the SP Bootflash Memory Upgrade Kit Figure Figure Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note...
Page 12
WS-X6624-FXS 24 PORT FXS ANALOG STATION WS-X6624-FXS 24 PORT FXS ANALOG STATION WS-X6348-RJ-45 V 48 PORT 10/100 BASE-T Ejector lever Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note ETHERNET SWITCHING MODULE INPUT OUTPU T FAIL INPUT OUTPU T FAIL Captive...
Page 13
Figure 3 Removing the Module from the Chassis (Horizontal Chassis Shown) Installing the CompactFlash Adapter To install the CompactFlash adapter, follow these steps: Locate the SP BOOTFLASH DIMM socket on the Supervisor Engine 720. (See Step 1 BOOTFLASH DIMM is on the left side of the Supervisor Engine 720 as you face the front of the board;...
Page 14
Step 3 Figure 5 Immediately place the DIMM in an antistatic bag. Step 4 Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note SP and RP DIMM Locations on the Supervisor Engine 720 RP Bootflash Figure 5, left view.) The DIMM will flip up in the socket. (See...
Page 15
Open the antistatic bag containing the SP CompactFlash adapter. Step 5 The SP CompactFlash adapter has a label attached to the CompactFlash identifying it as the SP Note CompactFlash adapter. Carefully align the CompactFlash adapter edge connector with the DIMM socket. Slide the Step 6 CompactFlash adapter edge connector at an angle into the socket.
Page 16
Fully open both ejector levers on the supervisor engine that is being installed. (See Step 3 Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note “Attaching Your ESD Grounding Strap” section on page 24 Figure 78-17277-05...
Page 17
Ejector lever fully extended 78-17277-05 EMI gasket INPUT OUTPU T FAIL WIT H INT EGR ATE D SW ITC H FAB RIC Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note Installing the SP Bootflash Memory Upgrade Kit INPUT OUTPU T FAIL...
Page 18
If the STATUS LED remains orange or turns red, the supervisor engine has not successfully completed the boot process and may have encountered an error. Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note Figure Figure 7.) Make sure that you align the sides of the...
Page 19
45 degrees with respect to the module faceplate. (See 78-17277-05 Figure Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note Installing the SP Bootflash Memory Upgrade Kit Press down Gap between the module...
Page 20
Installing the SP Bootflash Memory Upgrade Kit Figure 9 Positioning the Module in a Vertical Slot Chassis STATUS INPUT OUTPUT FAIL Insert module between slot guides Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note Ejector lever fully extended gasket gasket INPUT OUTPUT FAIL 78-17277-05...
Page 21
Power up your system. 78-17277-05 Gap between the module INPUT OUTPUT FAIL INPUT OUTPUT FAIL Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note Installing the SP Bootflash Memory Upgrade Kit EMI gasket and the module above it Figure 10.)
Release the CompactFlash adapter from the DIMM socket by simultaneously releasing the two locking Step 3 spring clips on either side of the DIMM socket. The CompactFlash adapter will flip up in the socket. Hold the CompactFlash adapter by its edges and carefully remove it from the DIMM socket.
Page 23
To make good electrical contact, you must fully insert the adapter’s connector pins into the CompactFlash; the pins should not be visible. Install the CompactFlash adapter in the DIMM socket using Step 4 Reinstall the Supervisor Engine 720 in the chassis following the Step 5 720”...
If your chassis does not have the system ground attached, you must install the system ground lug. • Refer to the online Catalyst 6500 Series Switches Installation Guide for the procedure. Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note 78-17277-05...
Page 25
If you are using an ESD wrist strap that is equipped with an alligator clip, attach the alligator clip directly over the head of the system ground lug screw or to the system ground lug barrel. 78-17277-05 Attaching Your ESD Grounding Strap Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note Figure 13):...
For safety, periodically check the resistance value of the antistatic strap. The measurement should be between 1 and 10 megohm (Mohm). Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note Attaching the ESD Wrist Strap Clip to the System Ground Lug Screw...
Solamente el personal calificado debe instalar, reemplazar o utilizar este equipo. Varning! Endast utbildad och kvalificerad personal bör få tillåtelse att installera, byta ut eller reparera denna utrustning. 78-17277-05 Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note Safety Warning Translations...
Page 28
Aviso Somente uma equipe treinada e qualificada tem permissão para instalar, substituir ou dar manutenção a este equipamento. Advarsel Kun uddannede personer må installere, udskifte komponenter i eller servicere dette udstyr. Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note 78-17277-05...
(EMI) que poderá danificar outro equipamento; e canalizam o fluxo do ar de refrigeração através do chassis. Não deverá operar o sistema sem que todas as placas, faces, protecções anteriores e posteriores estejam nos seus lugares. Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note 78-17277-05...
Page 30
(EMI), der kan forstyre andet udstyr, og de leder en strøm af kølig luft gennem chassiset. Betjen ikke systemet medmindre alle kort, frontplader, sidepaneler og bagpaneler er på plads. Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note 78-17277-05...
Page 32
Farlig spänning föreligger på bakplattan när systemet körs. Var försiktig vid service. Aviso O sistema em funcionamento emite tensão ou energia elétrica perigosa no painel traseiro. Seja cauteloso ao fazer a manutenção. Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note 78-17277-05...
Subscribe to the What’s New in Cisco Product Documentation as a Really Simple Syndication (RSS) feed and set content to be delivered directly to your desktop using a reader application. The RSS feeds are a free service and Cisco currently supports RSS version 2.0. Cisco CompactFlash Adapter for Bootflash Upgrade Installation Note 78-17277-05...
Page 34
Academy, Network Registrar, PCNow, PIX, PowerPanels, ProConnect, ScriptShare, SenderBase, SMARTnet, Spectrum Expert, StackWise, The Fastest Way to Increase Your Internet Quotient, TransPath, WebEx, and the WebEx logo are registered trademarks of Cisco Systems, Inc. and/or its affiliates in the United States and certain other countries.
Need help?
Do you have a question about the CompactFlash Adapter and is the answer not in the manual?
Questions and answers