Haier AD072XLEAA Operation And Installation Manual page 20

Duct type air conditioner
Table of Contents

Advertisement

Installation Procedure
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached
with the outdoor unit for details.
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions
attached with the outdoor unit. The added refrigerant shall be R22.
The adding procedure shall be aided with a measuring meter
for a specified amount of supplemented refrigerant
Requirement
Overfilling or underfilling of refrigerant will cause compressor
fault. The amount of the added refrigerant shall be as specified
in the instructions.
Connection of refrigerant pipe
Conduct flared connection work to connect all refrigerant pipes.
Pipe cutting and expanding
If the pipe is too long or the flare is damaged, it needs to be cut or expanded.
1. Pipe cutting
Pipe expansion dimensions as follows:
Pipe diameter Ø Size A (mm)
6.35 mm (1/4 " )
9.52 mm (3/8 " )
12.7 mm (1/2 " )
15.88 mm (5/8 " ) 1.4 ~ 2.2
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Connecting pipe
O.D.(mm)
Ø6.35
Ø9.52
Ø12.70
Ø15.88
2. Removing burrs
0.8 ~ 1.5
1.0 ~ 1.8
1.2 ~ 2.0
Installing torque
Increased installing
(N-m)
11.8 (1.2kgf-m)
24.5 (2.5kgf-m)
49.0 (5.0 kgf-m)
78.4 (8.0 kgf-m)
3.Insertion nut
Incorrect
Correct
Slope Damage Bur Partial Overlong
torque (N-m)
13.7 (1.4 kgf-m)
29.4 (3.0 kgf-m)
53.9 (5.5 kgf-m)
98.0 (10.0 kgf-m)
18
A
Pipe expander
4. Pipe expansion
Double-spanner
operation

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ad092xleaaAd122xleaaAd142xleaaAd212xleaa

Table of Contents