Pipe Connection - Haier AB092FCBHA User Manual

Built-in household cassette air conditioner
Hide thumbs Also See for AB092FCBHA:
Table of Contents

Advertisement

Pipe connection

(1)
Schematic diagram for unit connection
Indoor unit
Flared pipe connection
Indoor unit
(2)
Connection pipe dimensions:
Pipe Value
Liquid
Gaseous
Liquid
Gaseous
l Apply and tighten the nut.
3. Maximum length and height difference of connecting pipe
l Maximum length: 20m; Height difference: 10m
l To ensure efficiency, shortest possible pipe should be used.
Cautions for pipe connection
l Pipes free from twists, deformation, water, dust.
Dedicated tools for each R407C and R22
should be used and stored separately.
l Optimized radii of bends
l Insulation to be applied on all gaseous pipes
l Flared section free from cracks
(4) Pipe connection
Process
Apply refrigeration oil on the end of the pipe
to be connected and on the flared section.
Align the pipes to be connected and tighten
the nut. (See the figure)
Ensure that no foreign articles enter into the pipes.
Liquid pipe
Torque
18 N . m
6.35mm
25 N . m
9.52mm
42 N . m
9.52mm
50 N . m
12.7mm
Threads on the pipes may be damaged when tightening
if the pipes are not well aligned.
3-way Valve
Gaseous pipe
Manifold tube
2-way Valve
Flared pipe connection
90*0.5*
Spanner
Spanner
22
Outdoor uint
Joint
Nut