DAB EVOPLUS Instruction For Installation And Maintenance page 25

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 16
GB
ENGLISH
Low mains
E37
voltage (LP)
High mains
E38
voltage (HP)
Critical
overheating of
E32-e35
electronic parts
E43-e45;
Sensor signal
e54
absent
Protection against
E39-e40
overcurrent
E21-e30
Voltage Error
Twin
communication
E31
absent
E42
Dry operation
Motor excess
E56
temperature
f < 100 Hz ; f > 5
E57 ; e58
kHz
Energy Efficiency Index - EEI
The benchmark for the most efficient circulators is EEI ≤ 0,20
20
-
Switch off system power.Wait for the warning lights
on the control panel to go off, then power the
system again.
-
Check that the mains voltage is correct, if necessary
reset it at the plate values
-
Switch off system power.
-
Wait for the warning lights on the control panel to go
off, then power the system again.
-
Check that the mains voltage is correct, if necessary
reset it at the plate values.
-
Switch off system power.
-
Wait for the warning lights on the control panel to go
off.
-
Check that the system ventilation ducts are not
blocked and that the environment temperature of
the premises is correct.
-
Check sensor connection.
-
If the sensor is faulty, replace it.
-
Check that the circulator turns freely.
-
Check that any antifreeze added does not exceed
the maximum percentage of 30%.
-
Switch off system power.
-
Wait for the warning lights on the control panel to go
off, then power the system again.
-
Check that the mains voltage is correct, if necessary
reset it at the plate values.
-
Check that the twin communication cable is intact.
-
Check that both circulators are powered.
-
Put the system under pressure.
-
Switch off system power.
-
Wait for the motor to cool down.
-
Power the system again.
-
Check that the PWM external signal is operating
and connected as specified.