APPLICATION

The Honeywell Braukmann D05T Pressure Regulating Valve
is a high quality pressure regulating valve that maintains a
constant outlet pressure over a wide range of inlet supply
pressures. It is ideally suited for new residential and light
commercial construction, drip irrigation, and applications
requiring highly sensitive and accurate regulation.
The wide inlet pressure range of the D05T gives flexibility
without compromising reduced outlet pressure accuracy or
capacity. The superior balanced single-seat design maintains
a constant outlet pressure over a wide range of inlet
pressures. The noncorroding unitized cartridge insert contains
all the working parts and is easily replaceable.
The D05T is used for water or air regulation. It is not suitable
for steam.

FEATURES

• Non-corroding unitized cartridge contains all working
parts and is easily replaceable.
• Includes built-in strainer and thermal bypass.
• Balanced seat construction provides superior
pressure regulation.
• Inlet and outlet are internally threaded female NPT, and
externally threaded for use with union assemblies.
• One-year warranty.

SPECIFICATIONS

Model: D05T Pressure Regulating Valves
Construction Materials:
Body: Bronze.
Internal Parts: Stainless steel and engineered thermoplastic.
Regulator Mechanism: Fabric-reinforced diaphragm.
Inlet Pressure: 400 psi maximum.
Reduced Pressure Range: 15 to 90 psi.
Outlet Pressure: Factory set at 60 psi.
Differential: 14 psi minimum (inlet to outlet).
Temperature (Maximum):
Air: 158°F (70°C).
Water: 180°F (82°C).
Pipe Sizes: 3/4 in. and 1 in. available.
Application.........................................................................
Features ............................................................................
Specifications ....................................................................
Ordering Information .........................................................
Installation .........................................................................
Operation...........................................................................
Troubleshooting.................................................................
D05T Parts and Accessories .............................................
PRODUCT DATA
Contents
1
1
1
2
3
7
7
7
Put UPC Code Here
62-3021-03

Advertisement

loading

Summary of Contents for Honeywell D05T

  • Page 1: Table Of Contents

    The noncorroding unitized cartridge insert contains Water: 180°F (82°C). all the working parts and is easily replaceable. The D05T is used for water or air regulation. It is not suitable Pipe Sizes: 3/4 in. and 1 in. available. for steam.
  • Page 2: Ordering Information

    If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3: Installation

    Fig. 2) product to make sure the product is suitable for your application. The D05T is factory set to 60 psi. To change the outlet 3. Installer must be a trained, experienced service techni- pressure, turn the adjusting bolt counterclockwise cian.
  • Page 4 3. Remove the bonnet and washer using an adjustable wrench, socket, or box-end wrench. The working parts of the D05T, including diaphragm, valve 4. Remove the cartridge using two screwdrivers as levers. seat, and disk are all contained in a replaceable cartridge. To 5.
  • Page 5 D05T COMPACT DESIGN PRESSURE REGULATING VALVES LOOSEN LOCKNUT AND TURN ADJUSTING SCREW COUNTER CLOCKWISE REMOVE SPRING TENSION REMOVE BONNET USING AN ADJUSTABLE WRENCH, SOCKET, OR BOX END WRENCH REMOVE CARTRIDGE USING TWO ENSURE O-RINGS AND WASHER SCREWDRIVERS AS LEVERS ARE PROPERLY INSTALLED...
  • Page 6 D05T COMPACT DESIGN PRESSURE REGULATING VALVES ADJUSTING SCREW LOCKING NUT BONNET SPRING CUP SPRING WASHER CARTRIDGE O-RING SCREEN O-RING GASKET TAILPIECE TAILPIECE GASKET BODY M32171 Fig. 4. D05T exploded view. 62-3021—03...
  • Page 7: Operation

    See Fig. 5 for M32172 the internal construction of the D05T. Fig. 5. Internal construction of D05T. TROUBLESHOOTING Table 3 provides a troubleshooting guide for the D05T Pressure Regulating Valves. Table 3. Troubleshooting the D05T Pressure Regulating Valves. Problem Solution Whistling noise.
  • Page 8 D05T COMPACT DESIGN PRESSURE REGULATING VALVES Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive ® U.S. Registered Trademark Toronto, Ontario M1V 4Z9 © 2009 Honeywell International Inc.