Air Disinfection System Dear customer, You have graciously chosen an Orca GmbH product. This manual is intended for your safety in the handling of the system. Before mounting the components and putting the system into operation read the following statements carefully to avoid hazards caused by improper operation.
RIGINAL ACCESSORIES AND SPARE PARTS WARRANTIES ........................ 24 DISPOSAL OF COMPONENTS ..................24 ................................ 24 PRO TUBE ........................24 LECTRONIC BALLAST WITH SCREW JOINT ADDITIONAL INFORMATION ..................25 ........................... 25 DECLARATION OF CONFORMITY orca GmbH www.uvpro.de Seite 2 von 28...
A decline or absence in the disinfection performance. Users, installers, maintenance and cleaning personnel, must follow the instruction manual correctly and be made aware of possible dangers. What the symbols mean DANGER DANGER, ELECTRIC VOLTAGE HARMFUL UVC RADIATION INFORMATION orca GmbH www.uvpro.de Seite 3 von 28...
Years: 18+ UVC-Sterilization UVpro equipment’s intended use is sterilization using UVC light. Any other use is not permitted. No changes Changes made to the device from anyone other than orca GmbH are not permitted. orca GmbH www.uvpro.de Seite 4 von 28...
Recirculating Air Disinfection System V-lab Warranty only with original replacement parts In the case of maintenance, only original replacements parts (from orca) may be used. Ignoring this will make any warranty of the device void. Emission UVC-Radiation The radiation emitted is mostly UVC light with a wavelength of 254 nm (non-visible) λ...
Cables carrying electricity should be undisturbed The cables carrying electricity must be laid in a way that they are not bent, cut, underneath heavy objects, or in any other way at risk of destruction. orca GmbH www.uvpro.de Seite 6 von 28...
The effect can also manifest itself after some time. In cases of emergency, see a specialist. This is also applicable in cases of burnt skin caused by UVC radiation. orca GmbH www.uvpro.de Seite 7 von 28...
Technical changes reserved. System description The UVpro V-LAB Recirculating Air Disinfection System is suitable for the use in laboratories, patient rooms and medical practices. The unit can be mounted on the wall and is able to disinfect rooms up to 60 m²...
Page 11
Both of the service covers (4) are fixed through socket screws on the side of the housing. With mounting holes (11) on the reverse side of the protective housing, the unit can be attached on the wall. orca GmbH www.uvpro.de Seite 9 von 28...
3. ELECTRONIC COMPONENTS Electronic components The UVpro V-LAB Recirculating Air Disinfection System has a high-quality ballast (10) for optimum operation of the UVpro tube. In this way maximum power, high frequent ignition and high durability can be guaranteed. The high-frequency technology ensures a very high efficiency and low power consumption.
2 x UVC-radiation source, Type UVpro N30-2 Installation instructions The UVpro V-LAB has been carefully inspected and passed a function test before shipping. The high- quality packaging should prevent damage in transit. However, even with the most careful handling damage cannot be avoided completely. The UVC-tubes made of quartz glass are most susceptible to damage during transportation.
The easiest way to open the cover is to grip through the ventilation hole and drag the extreme front corners carefully. Now the visual protection can be removed. Pull it up for removal on the ends of the slats. orca GmbH www.uvpro.de Seite 13 von 28...
Page 16
Insert the new tube with retaining ring into the unit. Be sure, that the lamp tube end will be positioned correctly into the matching holder. The left service cover can also be removed to have a better view of the holder. orca GmbH www.uvpro.de Seite 14 von 28...
Page 17
Plug the tube into the holes and screw the retaining ring tight over the threads. Place the visual protection into correct position. Make sure that the notched edge of the metal frame is at the front. You can now fix the covers to the unit again. orca GmbH www.uvpro.de Seite 15 von 28...
UVC performance significantly. After 12,000 hours, the tubes have reached about 75 % of the output power and have to be exchanged. (See chapter 7.2 “Replacing tubes”). Sketch hole pattern orca GmbH www.uvpro.de Seite 16 von 28...
Due to this, it is possible that the display colour is purple when switching on the unit. As soon as the tubes reach the operating temperature, the display turns green. orca GmbH www.uvpro.de Seite 17 von 28...
Page 20
Recirculating Air Disinfection System V-lab Figure 1 - Menu navigation V-LAB orca GmbH www.uvpro.de Seite 18 von 28...
(off) it, set the starting time, the intensity, and the finishing time of the sterilisation. To confirm these settings, press enter. Four different settings (D1-D4) can be made per day that will repeat automatically every day orca GmbH www.uvpro.de Seite 19 von 28...
The tube runs for more than In older tubes (>12,000 hours) the gas The tube life is exceeded, the 12,000 hours. composition has changed, an ignition tube must be replaced. is no longer possible. orca GmbH www.uvpro.de Seite 20 von 28...
In the case of a visual control of the UVC-system, do not under any circumstances look at the ignited tubes without visual protection. Protect your skin through covering clothing, and never touch the tubes without wearing gloves. orca GmbH www.uvpro.de Seite 21 von 28...
While replacing tubes, check the seals, clean them, and replace them if damaged. In order to prevent fingerprints and fat traces on the tube, we recommend to always wear cloth gloves when working with the tubes. orca GmbH www.uvpro.de Seite 22 von 28...
In the procurement of spare parts, please make sure that it is original accessories of UVpro or the orca GmbH. Even with accessory components, we recommend that you use genuine parts from UVpro. The improper use of the equipment or the...
There are also free collection points in your local community where you can dispose of your exchanged or defective tubes. Electronic ballast with screw joint The square tube with electronic ballast can be disposed of in the electronic waste at the local garbage and recycling station. orca GmbH www.uvpro.de Seite 24 von 28...
10. ADDITIONAL INFORMATION EC declaration of conformity Declaration of conformity orca GmbH, Hungenbach 1D, D-51515 Kürten Phone: +49 2268/90830-0 Hereby we declare that the products listed below conform to, in their design, construction and sale, the basic safety and health requirements of the EC directives. Any unauthorized modification of the product will result in this declaration’s loss of validity.
Page 28
Recirculating Air Disinfection System V-lab orca GmbH www.uvpro.de Seite 26 von 28...
Page 29
Recirculating Air Disinfection System V-lab orca GmbH www.uvpro.de Seite 27 von 28...
Page 30
Recirculating Air Disinfection System V-lab orca GmbH www.uvpro.de Seite 28 von 28...