Installation - ADC DSX-1 User Manual

Interbay patch module
Hide thumbs Also See for DSX-1:
Table of Contents

Advertisement

ADCP-80-324
Issue 3, December 1996
Example 1: Single Lineup Patch
1.
Patch a DSX circuit on bay 6 of lineup 1 to a DSX circuit on bay 18 of lineup 1.
a) Install patch cords from the desired DSX circuit on bay 18 to an upper left set of
IN/OUT jacks on the bay 19 Interbay Patch Module. The busy indicator on all jacks
multipled to the selected jack circuit will flash for about 30 seconds and then remain
lit to indicate all patching jacks that may be used for the patch setup.
b) Install patch cords from the desired DSX circuit on bay 6 to the upper right set of
IN/OUT jacks on bay 7 corresponding to the flashing busy indicator. This will
extinguish busy indicators in bays 3 and 7. The busy indicators for jacks in the
circuit on bay 11 and 15 will remain lit to show this interbay circuit is in use. A plug
inserted into the jacks of this circuit on bays 11 or 15 will interrupt the patched
circuit.
Example 2: Multiple Lineup Patch
1.
Patch a DSX circuit on bay 1 of lineup 1 to a DSX circuit on bay 17 of lineup 3.
a) Install patch cords from the desired DSX circuit on bay 1 of lineup 1 to a lower right
set of IN/OUT jacks on lineup 1 bay 3 Interbay Patch Module. The busy indicator on
all jacks multipled to the selected jack circuit will flash for about 30 seconds and
then remain lit to indicate all patching jacks that may be used for the patch setup.
b) At bay 3 in lineup 3, install patch cords from the lower left set of IN/OUT jacks
corresponding to the flashing busy indicator, to an upper right set of IN/OUT jacks.
The busy indicator that was flashing for this patch circuit on bay 3 of lineup 3 will
be extinguished, and the busy indicator for the jacks multipled to the right set of
jacks will start flashing.
c) Install patch cords from the desired DSX circuit on bay 17 of lineup 3 to the upper
left set of IN/OUT jacks on bay 15 corresponding to flashing busy indicator. The
busy indicators for this patch circuit on bays 15 and 19 of lineup 3 will be
extinguished. The busy indicator for this patch circuit on bays 7 and 11 in lineup 3
and bay 3 in lineup 2 will remain lit to show that this patch circuit is in use.

4. INSTALLATION

Warning: To prevent electrical shock, never install telephone equipment in a wet
location or during a lightning storm. When installing or modifying telephone lines,
disconnect lines at the network interface before working with uninsulated lines or
terminals.
4.01
Installation of Interbay Patch Modules in various DSX-1 bays involves the
interconnection of the circuits on the terminal blocks at the back of the modules and connection
of battery and battery return leads for the LED indicators. Office power to the Interbay Patch
Module should be fused at 0.5 Amp. Use a minimum of 22 AWG wire when making power
connections.
Page 6
© 1996, ADC Telecommunications, Inc.