Figure 8. Typical Bantam Interbay Module Power Terminal Strip
A. Power and Ground Connections
4.02
A typical DSX-1/1C Interbay Patch Module power terminal strip is shown in
Connect each module to the fuse module as follows:
1.
Connect the –48V terminal on the module to a NEG (–) terminal on the fuse module
(white wire).
2.
Connect the GND terminal on the module to the corresponding POS (+) terminal on the
fuse module (black wire).
3.
Connect the CG terminal on the module to the office frame ground (green wire). This the
recommended chassis grounding procedure.
Note: The metal strap between the CG (Chassis Ground) and SG (Shield Ground)
terminals on the module may be removed to isolate the shield ground from the chassis
ground.
B. Interbay Interconnection Wiring
4.03
Interbay circuits are connected together using the 12 terminal blocks located at the back
of each module. Terminal block pins are connected to each jack circuit as shown in
upper six terminal blocks are connected to the left interbay jack circuits and the lower six
terminal blocks are connected to the right interbay circuits.
OUT
L
-48VGND
SGCG
OUT
R
1
1
2
3
4
5
6
7
8
9
A
B
C
IN
D
E
F
1
1
2
3
4
5
6
7
8
9
A
B
C
IN
D
E
F
© 1996, ADC Telecommunications, Inc.
ADCP-80-324
Issue 3, December 1996
5
6
10
1
2
A
B
C
D
E
F
5
6
10
1
2
3
A
B
C
D
E
F
8909-A
Figure
8.
Table
1. The
Page 7