Unit installation

6.4.2 To connect the piping on right side, right-back, or right-bottom

Installer reference guide
30
Drain hose extension. To extend the drain hose, use a field supplied hose with
inner Ø16 mm. Do NOT forget to use a heat insulation tube on the indoor section
of the extension hose.
a
a Drain hose supplied with the indoor unit
b Heat insulation tube (field supply)
c Extension drain hose
Ridgid polyvinyl chloride pipe. When connecting a ridgid polyvinyl chloride pipe
(nominal Ø13 mm) directly to the drain hose as with embedded piping work, use
a field supplied drain socket (nominal Ø13 mm).
a
a Drain hose supplied with the indoor unit
b Drain socket with nominal Ø13 mm (field supply)
c Ridgid polyvinyl chloride pipe (field supply)
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
1 Insert the drain hose in the drain pipe as shown in the following figure, so it
will NOT be pulled out of the drain pipe.
mm
INFORMATION
The factory default is right-side piping. For left-side piping, remove the piping from
the right side and install it on the left side.
1 Attach the drain hose with adhesive vinyl tape to the bottom of the
refrigerant pipes.
2 Wrap the drain hose and the refrigerant pipes together using insulation tape.
a
b
c
b
c
CTXA15+FTXA25~50(A)(B)2V1B(W)(S)(T)(B)
Daikin room air conditioner
4P518023-3K – 2022.05