H2O Leakage Sensor; Leakage Sensors, Model 2605 - NetPing Uniping server solution v3/SMS User Manual

Server solution
Table of Contents

Advertisement

Sensor Flex
First wire
Second Wire
Important! Sensors of a dry contact type, a supply voltage sensor, a leakage sensor, and others are plugged to
IO lines of a device. You can plug any eight sensors out of this set.
Important! A corresponding IO line should be set to an input mode in settings of a device.
A maximum allowable loop length is 100 meters.

H2O Leakage Sensor

A leakage sensor is plugged by a four-line wire according to the table:
Sensor Flex
Green
Yellow
Brown
White
Important! Sensors of a dry contact type, a supply voltage sensor, a leakage sensor, and others are plugged to
IO lines of a device. You can plug up to eight sensors of this set.
Important! A correspondent IO line should be set to an input mode in settings of a device.
A sensor is packaged with an inseparable cable, with connectors on the ends. A cable length can be increased with
the help
of flat cable extenders of
independently with the help of any wire with a minimum cross section of 0,4 mm
flat cable is 100 m.

Leakage Sensors, model 2605

A leakage sensor is plugged by a four-line wire according to the table:
[ENG] UniPing server solution v4/SMS & UniPing server solution v3, User guide -[USS] Sensors Plugin
UniPing server solution v4/SMS, UniPing server solution v3 Terminal Block
UniPing server solution v4/SMS, UniPing server solution v3 Terminal Block
RC-4 sensor, which are sequentially plugged one into another. Or it can be done
One of IO lines – 1 - 8
GND
One of IO lines – 1 - 8
GND
+5V
GND
2
. Maximum allowable length of a
[USS] Sensors Plugin
                             – 