[ENG] UniPing server solution v4/SMS & UniPing server solution v3, User guide -[USS] Sockets and Indication Elements
Voltage of the logic "0":  <0,9V
It is possible to plug relay coils to UniPing Server Solution v3/SMS IO lines directly. A voltage of triggering a relay
should be either 12 V or 5 V, and a triggering current - no more than 200mA. Control relay contacts are connected to
an IO terminal and to the terminal +12 V or 12 V relay or a +5 V terminal for a 5 V relay. A corresponding IO line
should be set to an output mode. When connecting several relays, there is a need to take into consideration that
their summed maximum triggering current should not exceed 200mA.

IO STATE LEDs

IO STATE LEDs
(see picture 1 and picture
2) signal about a status of the first four IO lines. When a LED is turned on, a
corresponding IO line is in a status logic 1, and a turned off LED means a logic status 0.

Thermo / IR Terminals

Picture 3 – Terminals «Thermo /
IR» (UniPing server solution
v4/SMS monitoring unit)
Picture 4 – Terminals «Thermo /
IR» (UniPing server solution
v3 monitoring unit)
A THERMO/IR terminal block is used to plug temperature sensors and an IR-transceiver. To make plugging sensors
convenient, connecting terminals are output to a front panel twice. Temperature sensors can be plugged into a left
terminal block as well as into a right one. An IR transceiver is plugged in parallel to temperature sensors into the
same terminals.