To Use Mode 2; Mode 1 (And Default Situation): Monitoring Settings - Daikin VRV IV i Series Installation And Operation Manual

Compressor unit for indoor installation
Hide thumbs Also See for VRV IV i Series:
Table of Contents

Advertisement

#
Action
5
Quit mode 1.
Example: 7‑segments display – Mode 1
(in case of 8 HP)
You can read out setting [1‑10] (=  the total number of connected
units (heat exchanger unit + indoor units)) as follows:
#
Action
1
Start from the default
situation.
2
Select mode 1.
3
Select setting 10.
("X×" depends on the setting
that you want to select.)
4
Display the value of setting
10.
(there are 8 units connected)
5
Quit mode 1.
16.1.6

To use mode 2

In mode 2 you can make field settings to configure the system. How
to do this differs slightly depending on the model.
Example: 7‑LEDs display – Mode 2
(in case of 5 HP)
You can change the value of setting [2‑8] (=  T
during cooling operation) to 4 (= 8°C) as follows:
#
Action
1
Start from the default
situation.
2
Select mode 2.
3
Select setting 8.
("X×" depends on the setting
that you want to select.)
4
Select value 4 (= 8°C).
a: Display the current value.
b: Change to 4. ("X×"
depends on the current
value, and the value that you
want to select.)
c: Enter the value in the
system.
d: Confirm. The system starts
operating according to the
setting.
5
Quit mode 2.
Example: 7‑segments display – Mode 2
(in case of 8 HP)
You can change the value of setting [2‑8] (=  T
during cooling operation) to 4 (= 8°C) as follows:
RKXYQ5T8 + RKXYQ8T7Y1B
VRV IV compressor unit for indoor installation
4P499900-1B – 2021.12
Button/display
BS1 [1×]
Button/display
BS1 [1×]
BS2 [X×]
BS3 [1×]
BS1 [1×]
16.1.7
In mode 1 (and in default situation) you can read out some
information. What you can read out differs depending on the model.
7‑LEDs display – Default situation (H1P OFF)
(in case of 5 HP)
target temperature
You can read out the following information:
e
Button/display
H6P
BS1 [5 s]
BS2 [X×]
(= binary 8)
a
BS3 [1×]
b
BS2 [X×]
c
BS3 [1×]
d
BS3 [1×]
BS1 [1×]
target temperature
e
#
Action
1
Start from the default
situation.
2
Select mode 2.
3
Select setting 8.
("X×" depends on the setting
that you want to select.)
4
Select value 4 (= 8°C).
a: Display the current value.
b: Change to 4. ("X×"
depends on the current
value, and the value that you
want to select.)
c: Enter the value in the
system.
d: Confirm. The system starts
operating according to the
setting.
5
Quit mode 2.
Mode 1 (and default situation): Monitoring
settings
Value / Description
Shows the status of low noise operation.
OFF
Unit is currently not operating under low noise
restrictions.
ON
Unit is currently operating under low noise
restrictions.
Low noise operation reduces the sound generated by the
unit compared to nominal operating conditions.
Low noise operation can be set in mode 2. There are two
methods to activate low noise operation of the compressor
unit and heat exchanger unit.
▪ The first method is to enable an automatic low noise
operation during night time by field setting. The unit will
operate at the selected low noise level during the
selected time frames.
▪ The second method is to enable low noise operation
based on an external input. For this operation an optional
accessory is required.
16 Configuration
Button/display
BS1 [5 s]
BS2 [X×]
a
BS3 [1×]
b
BS2 [X×]
c
BS3 [1×]
d
BS3 [1×]
BS1 [1×]
Installation and operation manual
31