15 Electrical installation
7 Take all the precautions mentioned in "16 Configuration" [ 4  28]
and "17 Commissioning" [ 4  36] into account.
8 Turn on the power of the indoor units, compressor unit and heat
exchanger unit.
9 Activate setting [2‑20] to start the manual additional refrigerant
charge mode. For details, see
settings" [ 4  33].
Result: The unit will start operation.
INFORMATION
The manual refrigerant charge operation will automatically
stop within 30 minutes. If charging is not completed after
30 minutes, perform the additional refrigerant charging
operation again.
INFORMATION
▪ When a malfunction is detected during the procedure
(e.g., in case of closed stop valve), a malfunction code
will be displayed. In that case, refer to
codes when charging
malfunction accordingly. Resetting the malfunction can
be done by pushing BS3. You can restart the
"Charging" instructions.
▪ Aborting the manual refrigerant charge is possible by
pushing BS3. The unit will stop and return to idle
condition.
10 Open valve A.
11 Charge refrigerant until the remaining determined additional
refrigerant amount is added, and then close valve A.
12 Press BS3 to stop the manual additional refrigerant charge
mode.
NOTICE
Make sure to open all stop valves after (pre-) charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
NOTICE
After adding the refrigerant, do not forget to close the lid of
the refrigerant charging port. The tightening torque for the
lid is 11.5 to 13.9 N•m.
14.4.4
Error codes when charging refrigerant
INFORMATION
If a malfunction occurs:
▪ In case of 5  HP: The error code is displayed on the
user interface of the indoor unit.
▪ In case of 8  HP: The error code is displayed on the
compressor unit's 7‑segments display and on the user
interface of the indoor unit.
If a malfunction occurs, close valve A immediately. Confirm the
malfunction code and take corresponding action,
codes" [ 4  38].
problems based on error
14.4.5
To fix the fluorinated greenhouse gases
label
1 Fill in the label as follows:
Installation and operation manual
26
"16.1.8  Mode 2: Field
"14.4.4  Error
refrigerant"  [ 4   26] and solve the
"19.1  Solving
Contains fluorinated greenhouse gases
RXXX
1
=
f
GWP: XXX
2
=
2
1
1
+
2
=
GWP × kg
=
1000
a
If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Quantity of fluorinated greenhouse gases of the total
refrigerant charge expressed as tonnes CO
f
GWP = Global warming potential
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO
2
Formula to calculate the quantity in CO
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge
label.
2 Fix the label on the inside of the compressor unit. There is a
dedicated place for it on the wiring diagram label.
15
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
15.1
About electrical compliance
Only for RKXYQ8
This equipment complies with:
▪ EN/IEC 61000‑3‑12 provided that the short-circuit power S
greater than or equal to the minimum S
point between the user's supply and the public system.
▪ EN/IEC
61000‑3‑12
=
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16 A and ≤75 A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected ONLY to a supply
with a short-circuit power S
minimum S
value.
sc
Model
RKXYQ8
15.2
Safety device requirements
NOTICE
When using residual current operated circuit breakers, be
sure to use a high-speed type 300  mA rated residual
operating current.
VRV IV compressor unit for indoor installation
a
kg
b
kg
c
kg
d
e
tCO
eq
2
equivalent.
2
equivalent.
equivalent
2
value at the interface
sc
European/International
Technical
greater than or equal to the
sc
Minimum S
value
sc
3329 kVA
RKXYQ5T8 + RKXYQ8T7Y1B
4P499900-1B – 2021.12
is
sc