The right-hand corner of the building is shown here. Dimen-
sions C and D are the minimum clearances that must be
maintained to the wall (→ Section 5.4). Dimension D varies
for the left-hand corner of the building.
4.1.4
Protective zone for wall installation in front
of a building wall
A
2100 mm
B
3100 mm
The protective zone below the product extends as far as the
floor.
Dimension C is the minimum clearance that must be main-
tained to the wall (→ Section 5.4).
20
A
B
C
200 mm/250 mm
D
1000 mm
4.1.5
Protective zone for wall installation in a
building corner
A
2100 mm
B
2600 mm
C
200 mm/250 mm
D
500 mm
The protective zone below the product extends as far as the
floor.
The right-hand corner of the building is shown here. Dimen-
sion C is the minimum clearance that must be maintained
to the wall (→ Section 5.4). Dimension D varies for the left-
hand corner of the building.
4.1.6
Protective zone for flat-roof installation
A
1000 mm
Dimension A is a clearance around the product.
Installation and maintenance instructions 0020330791_00
A
B
C
E
F
D
G
E
1000 mm
F
500 mm
G
1800 mm